Sensormatic Electronics victor
1. EXECUTIVE SUMMARY
- CVSS v3 7.8
- ATTENTION: Low attack complexity
- Vendor: Sensormatic Electronics, LLC, a subsidiary of Johnson Controls, Inc.
- Equipment: victor
- Vulnerability: Use of Hard-coded Credentials
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthorized elevation of privileges.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of victor, a video management system, are affected:
- victor: Versions 5.7 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798
The affected product contains an SIP component that uses a hard-coded password, which may allow a local, low-privileged user to access video information under certain circumstances.
CVE-2019-19492 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Ireland
3.4 RESEARCHER
Johnson Controls, Inc., reported this vulnerability to CISA.
4. MITIGATIONS
Johnson Controls has identified the following specific workarounds and mitigations users can apply to reduce the risk:
- Disable the SIP feature in versions prior to 5.7.1
- Upgrade victor to Version 5.7.1
For more detailed mitigation and product upgrade instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2021-19 v1
Further ICS security notices and product security guidance are located at the Johnson Controls product security website.
Users with additional questions may contact Johnson Controls Global Product Security.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
This product is provided subject to this Notification and this Privacy & Use policy.