ICS Advisory (ICSA-21-222-07)

Siemens SIMATIC NET CP

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 8.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC
  • Vulnerabilities: Out-of-Bounds Read, Use After Free

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow a remote attacker to access sensitive information and execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Siemens products are affected:

  • SIMATIC NET CP 1543-1 (Incl. SIPLUS NET variants): All versions prior to v3.0
  • SIMATIC NET CP 1545-1: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1    OUT-OF-BOUNDS READ CWE-125

The affected products are vulnerable to an out-of-bounds read vulnerability in mod_cap via the cap_text.ccap_to_text function, which could lead to information disclosure.

CVE-2020-9272 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.2    USE AFTER FREE CWE-416

A malicious attacker could corrupt the memory pool by interrupting the data transfer channel. This triggers a use-after-free condition in alloc_pool in pool.c, which could lead to remote code execution.

CVE-2020-9273 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends users update to the latest software version:

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Disable the embedded FTP server. The server is deactivated in the default configuration.
  • Limit access to Port 21/TCP to trusted IP addresses.

As a general security measure, Siemens strongly recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens operational guidelines for industrial security, and follow the recommendations in the product manual.

Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity

For more information about this issue, please see Siemens Security Advisory SSA-679335

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report