All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC, SINUMERIK
  • Vulnerabilities: Missing Encryption of Sensitive Data

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could lead to unauthorized access to sensitive data, privilege escalation, and configuration change.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Siemens products are affected:

  • SIMATIC Drive Controller Family: All versions
  • SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants): All versions
  • SIMATIC Field PG M5: All versions
  • SIMATIC Field PG M6: All versions
  • SIMATIC IPC127E: All versions
  • SIMATIC IPC427E: All versions
  • SIMATIC IPC477E: All versions
  • SIMATIC IPC477E Pro: All versions
  • SIMATIC IPC527GE: All versions
  • SIMATIC IPC547G: All versions
  • SIMATIC IPC627E: All versions
  • SIMATIC IPC647E: All versions
  • SIMATIC IPC677E: All versions
  • SIMATIC IPC847E: All BIOS versions prior to v25.02.10
  • SIMATIC ITP1000: All versions
  • SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (MLFB: 6ES7518-4AX00-1AC0, 6AG1518-4AX00-4AC0, incl. SIPLUS variant): All versions
  • SIMATIC S7-1500 CPU 1518F-4 PN-DP MFP (MLFB: 6ES7518-4FX00-1AC0): All versions
  • SINUMERIK 828D HW PPU.4: All versions
  • SINUMERIK MC MCU 1720: All versions
  • SINUMERIK ONE / SINUMERIK 840D sl Handheld Terminal HT 10: All versions
  • SINUMERIK ONE PPU 1740: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A race condition in the firmware for some Intel processors may allow a privileged user to enable escalation of privilege via local access.

CVE-2020-8670 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H).

3.2.2    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Improper buffer restrictions in a subsystem in the Intel CSME versions prior to 11.8.86, 11.12.86, 11.22.86, 12.0.81, 13.0.47, 13.30.17, 14.1.53, 14.5.32, and 15.0.22 may allow a privileged user to enable escalation of privilege via local access.

CVE-2020-8703 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:U/C:L/I:H/A:N).

3.2.3    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A race condition in a subsystem in the Intel LMS versions prior to 2039.1.0.0 may allow a privileged user to enable escalation of privilege via local access.

CVE-2020-8704 has been assigned to this vulnerability. A CVSS v3 base score of 6.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.4    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Improper initialization in the firmware for some Intel processors may allow a privileged user to enable escalation of privilege via local access.

CVE-2020-12357 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H).

3.2.5    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An out-of-bounds write in the firmware for some Intel processors may allow a privileged user to cause a denial-of-service condition via local access.

CVE-2020-12358 has been assigned to this vulnerability. A CVSS v3 base score of 6.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:C/C:L/I:N/A:H).

3.2.6    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An out-of-bounds read in the firmware for some Intel processors may allow an authenticated user to enable an escalation of privilege via local access.

CVE-2020-12360 has been assigned to this vulnerability. A CVSS v3 base score of 5.6 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:N/A:N).

3.2.7    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Improper input validation in the firmware for some Intel processors may allow an authenticated user to potentially enable a denial of service via local access.

CVE-2020-24486 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.8    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Out-of-bounds read in a subsystem in the Intel CSME versions prior to 12.0.81, 13.0.47, 13.30.17, 14.1.53, and 14.5.32 may allow a privileged user to enable information disclosure via local access.

CVE-2020-24506 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

3.2.9    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Improper initialization in a subsystem in the Intel CSME versions prior 11.8.86, 11.12.86, 11.22.86, 12.0.81, 13.0.47, 13.30.17, 14.1.53, 14.5.32, 13.50.11, and 15.0.22 may allow a privileged user to enable information disclosure via local access.

CVE-2020-24507 has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:N/A:N).

3.2.10   MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Improper isolation of shared resources in some Intel processors may allow an authenticated user to enable information disclosure via local access.

CVE-2020-24511 has been assigned to this vulnerability. A CVSS v3 base score of 5.6 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:N/A:N).

3.2.11    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

An observable timing discrepancy in some Intel processors may allow an authenticated user to enable information disclosure via local access.

CVE-2020-24512 has been assigned to this vulnerability. A CVSS v3 base score of 2.8 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:L/I:N/A:N).

3.2.12    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A domain-bypass transient execution vulnerability in some Intel Atom processors may allow an authenticated user to enable information disclosure via local access.

CVE-2020-24513 has been assigned to this vulnerability. A CVSS v3 base score of 5.6 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:N/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends updating to the latest software version:

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to the Siemens operational guidelines for industrial security and follow the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-309571

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

  • Ensure the least-privilege user principle is followed.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

This product is provided subject to this Notification and this Privacy & Use policy.

Please share your thoughts.

We recently updated our anonymous product survey; we'd welcome your feedback.