ICS Advisory (ICSA-21-063-01)

Rockwell Automation 1734-AENTR Series B and Series C

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: Rockwell Automation
  • Equipment: 1734-AENTR Series B and Series C
  • Vulnerabilities: Improper Access Control, Cross-site Scripting

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could lead to unauthorized data modification on the affected devices.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of 1734-AENTR are affected:

  • Series B, Versions 4.001 to 4.005, and 5.011 to 5.017 
  • Series C, Versions 6.011 and 6.012

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER ACCESS CONTROL CWE-284

The web interface of the 1734-AENTR communication module mishandles authentication for HTTP POST requests. A remote, unauthenticated attacker can send a crafted request that may allow for modification of the configuration settings. 

CVE-2020-14504 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.2    IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79

The web interface of the 1734-AENTR communication module is vulnerable to stored XSS. A remote, unauthenticated attacker could store a malicious script within the web interface that, when executed, could modify some string values on the homepage of the web interface. 

CVE-2020-14502 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:N/I:L/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Adam Eliot of the Loon Security Team reported these vulnerabilities to Rockwell Automation.

4. MITIGATIONS

Rockwell Automation recommends users update to the latest available patches: 

Please refer to Rockwell Automation’s security advisory PN1551 (requires login) for detailed information.

Rockwell Automation recommends the following network-based vulnerability mitigations for embedded products:

  • Utilize proper network infrastructure controls, such as firewalls, to help ensure that traffic from unauthorized sources are blocked.
  • Minimize network exposure for all control system devices and/or systems and ensure that they are not accessible from the Internet. For further information about the risks of unprotected Internet accessible control systems, please see Knowledgebase Article PN715
  • Locate control system networks and devices behind firewalls and isolate them from the business network.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks: 

No known public exploits specifically target these vulnerabilities. 


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report