ICS Advisory (ICSA-20-343-06)

Siemens XHQ Operations Intelligence

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 8.1
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: Siemens
  • Equipment: XHQ Operations Intelligence
  • Vulnerabilities: Exposure of Sensitive Information to an Unauthorized Actor, Cross-site Scripting, Basic XSS, SQL Injection, Relative Path Traversal, Cross-site Request Forgery

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to read sensitive information, modify web content, and perform cross-site scripting and cross-site request forgery on unsuspecting users.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of XHQ Operations Intelligence are affected:

  • XHQ: All versions prior to 6.1

3.2 VULNERABILITY OVERVIEW

3.2.1    EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

The application’s web server could expose non-sensitive information about the server’s architecture. This could allow an attacker to adapt further attacks to the version in place.

CVE-2019-19283 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.2    IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (‘CROSS-SITE SCRIPTING’) CWE-79

The web interface could allow cross-site scripting (XSS) attacks if an attacker is able to modify content of particular webpages, causing the application to behave in unexpected ways for legitimate users.

CVE-2019-19284 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:L/A:N).

3.2.3    IMPROPER NEUTRALIZATION OF SCRIPT-RELATED HTML TAGS IN A WEB PAGE (BASIC XSS) CWE-80

The web interface could allow injections that could lead to XSS attacks if unsuspecting users are tricked into accessing a malicious link.

CVE-2019-19285 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:L/A:N).

3.2.4    IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

The web interface could allow SQL injection attacks if an attacker is able to modify content of particular webpages.

CVE-2019-19286 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.5    RELATIVE PATH TRAVERSAL CWE-23

The web interface could allow attackers to traverse through the file system of the server based by sending specially crafted packets over the network without authentication.

CVE-2019-19287 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

3.2.6    IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (‘CROSS-SITE SCRIPTING’) CWE-79

The web interface could allow XSS attacks if unsuspecting users are tricked into accessing a malicious link.

CVE-2019-19288 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:L/A:N)

3.2.7    CROSS-SITE REQUEST FORGERY CWE-352

The web interface could allow a cross-site request forgery attack if an unsuspecting user is tricked into accessing a malicious link.

CVE-2019-19289 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N)

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends updating the XHQ Operations Intelligence product line to the newest version:

  • Update to v6.1:
    • Contact a service organization for further information on how to obtain the new version of XHQ. To identify a service organization, contact a Siemens hotline center.
  • Follow XHQ’s documentation on how to implement a secure configuration for the Internet Information Services (IIS).

Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following the recommendations in the product manuals.

Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity

For more information refer to SSA-712690

CISA recommends users take the following measures to protect themselves from social engineering attacks:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 