ICS Advisory (ICSA-20-329-02)

Fuji Electric V-Server Lite

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8
  • ATTENTION: Low skill level to exploit
  • Vendor: Fuji Electric
  • Equipment: V-Server Lite
  • Vulnerability: Out-of-bounds Write

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow for remote code execution on the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of V-Server Lite, a data collection and management service, are affected:

  • V-Server Lite, all versions prior to 3.3.24.0

3.2 VULNERABILITY OVERVIEW

3.2.1    OUT-OF-BOUNDS WRITE CWE-787

The affected product is vulnerable to an out-of-bounds write, which may allow an attacker to remotely execute arbitrary code. 

CVE-2020-25171 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Japan

3.4 RESEARCHER

Tran Van Khang - khangkito of VinCSS (Member of Vingroup), working with Trend Micro’s Zero Day Initiative, reported this vulnerability to CISA.

4. MITIGATIONS

Fuji Electric has released v3.3.25.0 of the software that can be downloaded from the company website (login required).

CISA recommends users take the following measures to protect themselves from social engineering attacks: 

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

This product is provided subject to this Notification and this Privacy & Use policy.

Please share your thoughts.

We recently updated our anonymous product survey; we'd welcome your feedback.