ICS Advisory (ICSA-20-308-02)

NEXCOM NIO50

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 5.3
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: NEXCOM
  • Equipment: NIO 50
  • Vulnerabilities: Improper Input Validation, Cleartext Transmission of Sensitive Information

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to view sensitive information and cause a denial-of-service condition due to improper input validation.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

All versions of NEXCOM NIO 50 are affected.

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER INPUT VALIDATION CWE-20

The affected product does not properly validate input, which may allow an attacker to execute a denial-of-service attack.

CVE-2020-25151 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.2    CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

The affected product transmits unencrypted sensitive information, which may allow an attacker to access this information.

CVE-2020-25155 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Multiple sectors
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Zero Day Initiative reported these vulnerabilities to CISA.

4. MITIGATIONS

NEXCOM no longer sells or maintains NIO 50 and considers it to be an end-of-life product.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report