Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 5.5
- ATTENTION: Low skill level to exploit
- Vendor: Siemens
- Equipment: Siemens Industrial Products containing certain processors
- Vulnerability: Exposure of Sensitive Information to an Unauthorized Actor
2. UPDATE INFORMATION
This updated advisory is a follow-up to the advisory update titled ICSA-20-252-07 Siemens Industrial Products (Update A) that was published October 13, 2020, to the ICS webpage on us-cert.gov.
3. RISK EVALUATION
Successful exploitation of this vulnerability may allow an authenticated user to enable information disclosure via local access.
4. TECHNICAL DETAILS
4.1 AFFECTED PRODUCTS
- SIMATIC Field PG M4: All versions.
- SIMATIC Field PG M5: All versions
- SIMATIC Field PG M6: All versions
- SIMATIC IPC3000 SMART: All versions
- SIMATIC IPC347E: All versions
- SIMATIC IPC427D (incl. SIPLUS variants): All versions
- SIMATIC IPC427E (incl. SIPLUS variants): All versions
- SIMATIC IPC477D: All versions
--------- Begin Update B Part 1 of 2 ---------
- SIMATIC IPC427E (incl. SIPLUS variants): All BIOS versions prior to 21.01.14
- SIMATIC IPC477E: All BIOS versions prior to 21.01.14
- SIMATIC IPC477E Pro: All BIOS versions prior to 21.01.14
--------- End Update B Part 1 of 2 ---------
- SIMATIC IPC527G: All versions
- SIMATIC IPC547E: All versions
- SIMATIC IPC547G: All versions
- SIMATIC IPC627D: All versions
- SIMATIC IPC627E: All versions
- SIMATIC IPC647D: All versions
- SIMATIC IPC647E: All versions
- SIMATIC IPC677D: All versions
- SIMATIC IPC677E: All versions
- SIMATIC IPC827D: All versions
- SIMATIC IPC847D: All versions
- SIMATIC IPC847E: All versions
- SIMATIC ITP1000: All versions
- SIMOTION P320-4E: All versions
- SIMOTION P320-4S: All versions
- SIMATIC IPC627E: All BIOS versions prior to v25.02.06
- SIMATIC IPC647E: All BIOS versions prior to v25.02.06
- SIMATIC IPC677E: All BIOS versions prior to v25.02.06
- SIMATIC IPC847E: All BIOS versions prior to v25.02.06
- SINUMERIK 828D (PPU.4 / PPU1740): All versions (Versions removed from the scope of this advisory)
- SINUMERIK 840D sl (NCU730.3B): All versions (Versions removed from the scope of this advisory)
- SINUMERIK ONE (NCU1750 / NCU1760): All versions (Versions removed from the scope of this advisory)
4.2 VULNERABILITY OVERVIEW
4.2.1 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200
Incomplete cleanup from specific special register read operations in some Intel processors may allow an authenticated user to potentially enable information disclosure via local access.
CVE-2020-0543 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).
4.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
4.4 RESEARCHER
Alyssa Milburn, Hany Ragab, Kaveh Razavi, Herbert Bos, and Cristiano Giuffrida from the VUSec group at VU Amsterdam reported this vulnerability to Intel.
5. MITIGATIONS
Siemens recommends updating the following products to the most current BIOS version where available:
- SIMATIC IPC627E IPC647E, IPC677E, and IPC847E BIOS to v25.02.06
--------- Begin Update B Part 2 of 2 ---------
- SIMATIC IPC427E, IPC477E, and IPC477E Pro: Update BIOS to v21.01.14
--------- End Update B Part 2 of 2 ---------
Siemens is preparing further updates and recommends the following specific workarounds and mitigations users can apply to reduce the risk until fixes are available.
- As a prerequisite for an attack, an attacker must be able to run untrusted code on affected systems. Siemens recommends limiting the possibilities to run untrusted code if possible.
- Applying a defense-in-depth concept can help to reduce the probability that untrusted code is run on the system. Siemens recommends applying the defense-in-depth concept.
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for Industrial Security, and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/Industrialsecurity
For more information on these vulnerabilities and the associated mitigations, please see Siemens security advisory SSA-534763
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable from adjacent networks.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.