Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 6.5
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: Siemens
- Equipment: SIMATIC HMI
- Vulnerabilities: Improper Restriction of Excessive Authentication Attempts, Authentication Bypass by Primary Weakness
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Siemens SIMATIC HMI Products are affected:
- SIMATIC HMI Basic Panels, 2nd Generation (incl. SIPLUS variants): Version 14 and above and versions prior to XX are affected by CVE-2020-15786
- SIMATIC HMI Comfort Panels (incl. SIPLUS variants): All versions are affected by CVE-2020-15786
- SIMATIC HMI Mobile Panels: All versions are affected by CVE-2020-15786
- SIMATIC HMI United Comfort Panels: All versions
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER RESTRICTION OF EXCESSIVE AUTHENTICATION ATTEMPTS CWE-307
Affected devices insufficiently block excessive authentication attempts. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
CVE-2020-15786 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L).
3.2.2 AUTHENTICATION BYPASS BY PRIMARY WEAKNESS CWE-305
Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
CVE-2020-15787 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Energy
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Joseph Gardiner from Bristol Cyber Security Group, University of Bristol, reported these vulnerabilities to Siemens.
4. MITIGATIONS
Siemens is preparing updates and recommends specific countermeasures for products where updates are not yet available. Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:
- Apply defense-in-depth strategies outlined here: https://www.siemens.com/cert/operational-guidelines-industrial-security
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.
For additional information, please refer to Siemens Security Advisory SSA-542525
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.