Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 7.8
- ATTENTION: Low skill level to exploit
- Vendor: ABB
- Equipment: Device Library Wizard
- Vulnerability: Insecure Storage of Sensitive Information
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow a low-level user to escalate privileges and fully compromise the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following products of Device Library Wizard are affected:
- Device Library Wizard: Versions 6.0.X, 6.0.3.1, and 6.0.3.2
3.2 VULNERABILITY OVERVIEW
3.2.1 INSECURE STORAGE OF SENSITIVE INFORMATION CWE-922
The software writes sensitive system information to an unprotected file, and a low-privileged user could read confidential data from such a file. This could allow the user to take control of the product
CVE-2020-8482 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
William Knowles of Applied Risk reported this vulnerability to ABB.
4. MITIGATIONS
ABB recommends users apply one of the following updates:
- Device Library Wizard Version 6.0.3.2 RU1
- Device Library Wizard Version 6.0.3.3
- Device Library Wizard Version 6.1.X and later
ABB recommends disabling interactive logon for the service account (both local and remote).
For more information please refer to ABB’s Cybersecurity Advisory.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Follow the principle of least privilege.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.