ICS Advisory (ICSA-20-140-02)

Emerson OpenEnterprise

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 10.0
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: Emerson
  • Equipment: OpenEnterprise SCADA Software
  • Vulnerabilities: Missing Authentication for Critical Function, Improper Ownership Management, Inadequate Encryption Strength

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker access to OpenEnterprise configuration services or access passwords for OpenEnterprise user accounts.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Emerson reports that these vulnerabilities affect the following OpenEnterprise SCADA Software:

  • OpenEnterprise: all versions through 3.3.4

3.2 VULNERABILITY OVERVIEW

3.2.1    MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected components may allow an attacker to run an arbitrary commands with system privileges or perform remote code execution via a specific communication service. 

CVE-2020-10640 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.2.2    IMPROPER OWNERSHIP MANAGEMENT CWE-282

Inadequate folder security permissions may allow modification of important configuration files, which could cause the system to fail or behave in an unpredictable manner.

CVE-2020-10632 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H).

3.2.3    INADEQUATE ENCRYPTION STRENGTH CWE-326

Inadequate encryption may allow the passwords for OpenEnterprise user accounts to be obtained.

CVE-2020-10636 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy, Chemical, Critical Manufacturing, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Roman Lozko of Kaspersky reported these vulnerabilities to Emerson.

4. MITIGATIONS

Emerson recommends all users upgrade to OpenEnterprise 3.3, Service Pack 5 (3.3.5), to resolve these issues. OpenEnterprise Service Packs are available to users with access to the Emerson SupportNet system (login required). Details will be found in the downloads area.

Please send any questions via a SupportNet ticket or by contacting Emerson at US 800-537-9313. For users outside of the United States, please use international toll-free numbers.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Ensure the least-privilege user principle is followed.
  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 