Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 6.5
- ATTENTION: Low skill level to exploit
- Vendor: LCDS - Leão Consultoria e Desenvolvimento de Sistemas Ltda ME
- Equipment: LAquis SCADA
- Vulnerabilities: Exposure of Sensitive Information to an Unauthorized Actor, Improper Input Validation
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow unauthorized attackers to view sensitive information and create files in arbitrary locations.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of LAquis SCADA are affected:
- LAquis SCADA Versions 4.3.1 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200
The affected product is vulnerable to sensitive information exposure by unauthorized users.
CVE-2020-10618 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).
3.2.2 IMPROPER INPUT VALIDATION CWE-20
The affected product is vulnerable to arbitrary file creation by unauthorized users.
CVE-2020-10622 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Commercial Facilities, Energy, Food and Agriculture, Transportation Systems, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: South America
- COMPANY HEADQUARTERS LOCATION: Brazil
3.4 RESEARCHER
Natnael Samson (@NattiSamson) working with Trend Micro’s Zero Day Initiative reported these vulnerabilities to CISA.
4. MITIGATIONS
LCDS recommends users update to the latest version of LAquis SCADA.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
- Ensure that principles of least privilege are followed.
- Restrict physical access to critical systems.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.