All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 9.0
- ATTENTION: Exploitable remotely
- Vendor: Siemens
- Equipment: TIM 3V-IE and 4R-IE Family Devices
- Vulnerability: Active Debug Code
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated attacker with network access to gain full control over the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of TIM communication modules for SIMATIC S7-300 and S7-400 devices are affected:
- TIM 3V-IE (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 3V-IE Advanced (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 3V-IE DNP3 (incl. SIPLUS NET variants): all versions prior to v3.3
- TIM 4R-IE (incl. SIPLUS NET variants): all versions prior to v2.8
- TIM 4R-IE DNP3 (incl. SIPLUS NET variants): all versions prior to v3.3
3.2 VULNERABILITY OVERVIEW
3.2.1 ACTIVE DEBUG CODE CWE-489
The affected versions contain an open debug port that is available under specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2
If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device.
CVE-2019-10939 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has released updates for the affected products and recommends users update to the new version.
- TIM 3V-IE (incl. SIPLUS NET variants) and TIM 3V-IE Advanced (incl. SIPLUS NET variants): Update to v2.8
- TIM 3V-IE DNP3 (incl. SIPLUS NET variants): Update to v3.3
- TIM 4R-IE (incl. SIPLUS NET variants): Update to v2.8
- TIM 4R-IE DNP3 (incl. SIPLUS NET variants): Update to v3.3
Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:
- Set the IP of the device to anything other than 192.168.1.2
- Limit access to Port 17185/UDP of an affected device (e.g., cell-protection firewall or corporate firewall) to reduce the risk.
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following the recommendations in the product manuals.
Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity
For more information on this vulnerability and more detailed mitigation instructions, please see Siemens security advisory SSA-359303
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. High skill level is needed to exploit.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.