Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 7.5
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: GE/Emerson
- Equipment: PACSystems RX3i
- Vulnerability: Improper Input Validation
2. RISK EVALUATION
Successful exploitation of this vulnerability could cause the system to change to halt-mode, resulting in a denial-of-service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Emerson reports this vulnerability affects the following GE PACSystem products and versions:
- CPE100: All versions prior to R9.85
- CPE115: All versions prior to R9.85
- CPE302: All versions prior to R9.90
- CPE305: All versions prior to R9.90
- CPE310: All versions prior to R9.90
- CRU320: (End of Life; Upgrade to CPE330)
- CPE330: All versions prior to R9.90
- CPE400: All versions prior to R9.90
- CPL410: All versions prior to R9.90
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER INPUT VALIDATION CWE-20
Sending specially manipulated packets can cause the module state to change to halt-mode, resulting in a denial-of-service condition. An operator must reboot the CPU module after removing battery or energy pack to recover from halt-mode.
CVE-2019-13524 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agricultural, Government Facilities, Information Technology, Transportation Systems, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Jin Kyung Lee and Yeop Chang of NSR (National Security Research Institute) reported this vulnerability to CISA.
4. MITIGATIONS
Emerson has acquired the affected products from GE. All inquiries should be directed to Emerson:
1-888-565-4155
1-434-214-8532 (if toll free 800 option is unavailable)
Tech Support:
Sales/Order Support:
Emerson recommends users upgrade to the following versions:
- Version R9.85
- Version R9.90
- CPE302 – Upgrade Kit: CPE302_FW9_90_41G2552-FW01-000-A3.zip
- CPE305 – Upgrade Kit: CPE305_FW9_90_41G1733-MS10-000-A20.zip
- CPE310 – Upgrade Kit: CPE310_FW9_90_41G1734-MS10-000-A20.zip
- CPE330 – Upgrade Kit: CPE330_FW9_90_41G2016-FW01-000-A16.zip
- CPE400 – Upgrade Kit: CPE400_FW9_90_41G2376-FW01-000-A7.zip
- CPL410 – Upgrade Kit: CPL410_FW9_90_41G2617-FW01-000-A3.zip
- Emerson notes that CPU/CRU320 has reached end of life. They recommend users upgrade to CPE330.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.