ICS Advisory (ICSA-19-204-01)

Mitsubishi Electric FR Configurator2

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 7.1
  • ATTENTION: Low skill level to exploit
  • Vendor: Mitsubishi Electric
  • Equipment: Mitsubishi Electric FR Configurator2
  • Vulnerabilities: Improper Restriction of XML External Entity Reference, Uncontrolled Resource Consumption

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may enable arbitrary files to be read or cause a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Mitsubishi FR Configurator2, used for configuring Mitsubishi variable frequency drives, are affected:

  • FR Configurator2 Version 1.16S and prior

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

This vulnerability is triggered when input passed to the XML parser is not sanitized while parsing the XML project and/or template file (.frc2). Once a user opens the file, the attacker could read arbitrary files.

CVE-2019-10976 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:H). 

3.2.2    UNCONTROLLED RESOURCE CONSUMPTION CWE-400

This vulnerability can be triggered when an attacker provides the target with a rogue project file (.frc2). Once a user opens the rogue project, CPU exhaustion occurs, which causes the software to quit responding until the application is restarted.

CVE-2019-10972 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Japan

3.4 RESEARCHER

Applied Risk reported these vulnerabilities to CISA.

4. MITIGATIONS

Mitsubishi Electric has released Version 1.17T for the reported vulnerabilities. Additional information about the vulnerabilities and how to obtain the update can be found at the following location:

https://www.mitsubishielectric.com/fa/download/software/drv/inv/vulnerability-protection/2019-001.pdf

Additional information about the vulnerabilities or Mitsubishi Electric's compensating control is available by contacting a local Mitsubishi Electric representative, which can be found at the following location:

https://us.mitsubishielectric.com/fa/en/about-us/distributors

CISA recommends users take the following measures to protect themselves from social engineering attacks: 

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

This product is provided subject to this Notification and this Privacy & Use policy.

Please share your thoughts.

We recently updated our anonymous product survey; we'd welcome your feedback.