Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 6.5
- ATTENTION: Low skill level to exploit
- Vendor: AVEVA
- Equipment: Vijeo Citect and CitectSCADA
- Vulnerability: Insufficiently Protected Credentials
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow a locally authenticated user to obtain Citect user credentials.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Vijeo Citect and CitectSCADA, a Supervisory Control and Data Acquisition (SCADA) software, are affected:
- Vijeo Citect 7.30 and 7.40
- CitectSCADA 7.30 and 7.40
3.2 VULNERABILITY OVERVIEW
3.2.1 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522
A vulnerability has been identified that may allow an authenticated local user access to Citect user credentials.
CVE-2019-10981 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United Kingdom
3.4 RESEARCHER
VAPT Team, C3i Center, and IIT Kanpur reported this vulnerability to AVEVA.
4. MITIGATIONS
AVEVA recommends all affected users download and upgrade to CitectSCADA 2018 as soon as possible. Available at (login required):
https://softwaresupportsp.schneider-electric.com/#/producthub/details?id=51141
AVEVA’s Security Advisory can be viewed at:
https://sw.aveva.com/hubfs/assets-2018/pdf/security-bulletin/SecurityAdvisory_LFSec136.pdf
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Ensure that least privilege is implemented throughout the system.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.