All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 7.3
- ATTENTION: Low skill level to exploit
- Vendor: Omron
- Equipment: Network Configurator for DeviceNet
- Vulnerability: Untrusted Search Path
2. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled ICSA-19-134-01 Omron Network Configurator for DeviceNet that was published May 14, 2019, on the ICS webpage on us-cert.gov.
3. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to achieve arbitrary code execution under the privileges of the application.
4. TECHNICAL DETAILS
4.1 AFFECTED PRODUCTS
The following versions of Network Configurator for DeviceNet Safety are affected:
- Network Configurator for DeviceNet Safety 3.41 and prior
4.2 VULNERABILITY OVERVIEW
4.2.1 UNTRUSTED SEARCH PATH CWE-426
The application searches for resources by means of an untrusted search path that could execute a malicious .dll file not under the application's direct control and outside the intended directories.
CVE-2019-10971 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).
4.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Japan
4.4 RESEARCHER
The researcher with the handle n0b0dy sent information to CISA, leading to the discovery of this vulnerability.
5. MITIGATIONS
--------- Begin Update A Part 1 of 1 ---------
Omron has released Version 3.42 of Network Configurator for DeviceNet Safety to address the reported vulnerability. Users can download the latest version of Network Configurator for DeviceNet Safety.
Omron has recommended applying the following for further mitigation:
- Remove or restrict directories listed in the PATH environment variable.
- Ensure system directories are writable only by administrators, which is Windows’ initial configuration.
- Operate Windows PCs with a standard user (non-administrator) account. Administrator accounts should be used only when necessary.
- Ensure there are no untrusted files in the directory where the application is installed.
- Confirm no untrusted files exist in the same directory before double-clicking project file or copying the project file to a trusted directory or a newly-created temporary directory.
--------- End Update A Part 1 of 1 ---------
CISA also recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.