ICS Advisory (ICSA-19-094-01)

Omron CX-Programmer

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 6.6
  • ATTENTION: Low skill level to exploit
  • Vendor: Omron
  • Equipment: CX-Programmer within CX-One
  • Vulnerability: Use After Free

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to execute code under the privileges of the application.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following version of CX-Programmer within CX-One is affected:

  • CX-Programmer v9.70 and prior
  • Common Components January 2019 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1    USE AFTER FREE CWE-416

When processing project files, the application fails to check if it is referencing freed memory. An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application.

CVE-2019-6556 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Japan

3.4 RESEARCHER

Esteban Ruiz (mr_me) of Source Incite, working with Trend Micro’s Zero Day Initiative, reported this vulnerability to NCCIC.

4. MITIGATIONS

Omron has released an updated version of CX-One to address the vulnerability. This release is available through the CX-One auto-update service.

  • CX-Programmer Version 9.71
  • Common Components April 2019

NCCIC recommends that users take the following measures to protect themselves from social engineering attacks:

NCCIC also recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

This product is provided subject to this Notification and this Privacy & Use policy.

Please share your thoughts.

We recently updated our anonymous product survey; we'd welcome your feedback.