All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 8.8
- ATTENTION: Low skill level to exploit
- Vendor: AVEVA
- Equipment: Wonderware System Platform
- Vulnerability: Insufficiently Protected Credentials
2. RISK EVALUATION
This vulnerability could allow unauthorized access to the credentials for the ArchestrA Network User Account.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Wonderware System Platform, a unifying supervisory platform, are affected:
- Wonderware System Platform 2017 Update 2 and prior.
3.2 VULNERABILITY OVERVIEW
3.2.1 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522
Wonderware System Platform uses an ArchestrA network user account for authentication of system processes and inter-node communications. A user with low privileges could make use of an API to obtain the credentials for this account.
CVE-2019-6525 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United Kingdom
3.4 RESEARCHER
Vladimir Dashchenko from Kaspersky Lab reported this vulnerability to AVEVA.
4. MITIGATIONS
AVEVA recommends users using Wonderware System Platform 2017 Update 2 and prior should upgrade to System Platform 2017 Update 3 as soon as possible. This update can be downloaded from the following location (login required):
https://softwaresupportsp.schneider-electric.com/#/producthub/details?id=52332
AVEVA has published Security Bulletin LFSEC00000135. It can be found at the following location:
https://sw.aveva.com/hubfs/assets-2018/pdf/security-bulletin/SecurityBulletin_LFSec135.pdf
AVEVA recommends that users secure industrial control systems according to NIST SP 800-82 Rev. 2:
https://csrc.nist.gov/publications/detail/sp/800-82/rev-2/final
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.