All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 7.1
- ATTENTION: Low skill level to exploit
- Vendor: McAfee
- Equipment: SINAMICS PERFECT HARMONY GH180
- Vulnerability: Improper Access Control
2. RISK EVALUATION
These files can be executed to compromise the HMI, and by extension, the drive system.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens has analyzed the vulnerability and has determined this vulnerability applies to the following HMIs:
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR32 with option A30 (HMIs 12 inch or larger)
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR42 with option A30 (HMIs 12 inch or larger)
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR52 with option A30 (HMIs 12 inch or larger
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR325 (High Availability)
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR32 with option A30 (HMIs 12 inch or larger) where the HMI is operating under Microsoft Windows XP
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR42 with option A30 (HMIs 12 inch or larger) where the HMI is operating under Microsoft Windows XP
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR52 with option A30 (HMIs 12 inch or larger) where the HMI is operating under Microsoft Windows XP
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR325 (High Availability) where the HMI is operating under Microsoft Windows XP.
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER ACCESS CONTROL CWE-284
HMIs with this vulnerability can be compromised via local attack using removable USB storage devices to transfer malicious files. The executable files from a hard drive solidified by MACC (McAfee Application and Change Control) can be executed on the system that did not generate the inventory.
CVE-2018-6690 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Energy, Food and Agriculture, Healthcare and Public Health, Transportation, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
McAfee reported this vulnerability to Siemens.
4. MITIGATIONS
McAfee has issued Security Bulletin SB10250 to address this vulnerability in MACC. SINAMICS PERFECT HARMONY GH180 Drives with HMIs produced between November 4, 2015 and October 9, 2018, use MACC as part of their software package, if option A30 was part of the order.
For compatibility reasons, Siemens advises the installation of MACC 8.2.0 instead of Version 8.0.0, hotfix 5 as mentioned in SB10250.
For the following products, Siemens recommends users upgrade to MACC v8.2.0 or greater using recommendations from McAfee to fix the vulnerability.
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR32 with option A30 (HMIs 12 inch or larger)
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR42 with option A30 (HMIs 12 inch or larger)
- SINAMICS PERFECT HARMONY GH180 Drives: Serial numbers beginning MLFB 6SR52 with option A30 (HMIs 12 inch or larger)
The update can be located here:
https://kc.mcafee.com/corporate/index?page=content&id=SB10250
For the remaining products, and until updates can be applied, Siemens recommends the following workarounds to reduce risk:
For the remaining products, and until updates can be applied, Siemens recommends the following workarounds to reduce risk:
- Protect local access to the drive.
- Ensure USB based storage media is blank and malware free before connecting to the drive.
- Apply cell protection concept and implement defense-in-depth.
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
https://www.siemens.com/industrialsecurity
For more information on this vulnerability and associated software updates, please see Siemens security advisory SSA-674165 on their website:
https://www.siemens.com/cert/advisories
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.