ICS Advisory (ICSA-18-275-03)

Entes EMG 12

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low skill level to exploit
  • Vendor: Entes
  • Equipment: EMG 12
  • Vulnerabilities: Improper Authentication, Information Exposure Through Query Strings in GET Request

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow attackers to gain unauthorized access and could allow the ability to change device configuration and settings.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of EMG 12, an Ethernet Modbus Gateway, are affected:

  • EMG12 Ethernet Modbus Gateway Firmware Version 2.57 and prior.

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER AUTHENTICATION CWE-287

The application uses a web interface where it is possible for an attacker to bypass authentication with a specially crafted URL. This could allow for remote code execution.  

CVE-2018-14826 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.2    INFORMATION EXPOSURE THROUGH QUERY STRINGS IN GET REQUEST CWE-598

An information exposure through query strings vulnerability in the web interface has been identified, which may allow an attacker to impersonate a legitimate user and execute arbitrary code.

CVE-2018-14822 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Turkey

3.4 RESEARCHER

Can Demirel of Biznet Bilisim reported this vulnerability to NCCIC.

4. MITIGATIONS

Entes recommends that users update to the latest available firmware version. This can be requested by calling, tel:+902163130110 or by email at teknikdestek@entes.com.tr

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report