All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 8.0
- ATTENTION: Exploitable remotely/Low skill level to exploit/Public exploits are available
- Vendor: WAGO
- Equipment: e!DISPLAY Web-Based-Management (WBM)
- Vulnerabilities: Cross-site Scripting, Unrestricted Upload of File with Dangerous Type, and Incorrect Permissions for Critical Resource
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to execute code in the context of the user, execute code within the user’s browser, place malicious files within the filesystem, and replace existing files to allow privilege escalation.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of WAGO e!DISPLAY, an HMI, running firmware FW 01 are affected:
- 762-3000,
- 762-3001,
- 762-3002, and
- 762-3003
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79
Authenticated and unauthenticated users can send specially crafted requests to the web server, which allows code injection within the WBM. The code will be rendered and/or executed within the user’s browser.
CVE-2018-12981 has been assigned to this vulnerability. A CVSS v3 base score of 8.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).
3.2.2 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434
This vulnerability allows an authenticated user to upload arbitrary files to the file system with the permissions of the web server.
CVE-2018-12980 has been assigned to this vulnerability. A CVSS v3 base score of 8.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).
3.2.3 INCORRECT PERMISSION FOR CRITICAL RESOURCE CWE-732
Weak permissions allow an authenticated user to overwrite critical files by abusing the unrestricted file upload in the WBM.
CVE-2018-12979 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy, and Transportation Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
T. Weber of SEC Consult reported these vulnerabilities to CERT@VDE, who reported them to NCCIC.
4. MITIGATIONS
WAGO recommends affected users update to the latest firmware (FW 02). Contact WAGO support for update files and specific instructions.
WAGO also recommends the following mitigations:
- Update the device to the latest firmware.
- Restrict network access to the device.
- Do not directly connect the device to the Internet.
- Restrict the number of users with access to the device to a minimum.
- Change the default passwords of devices.
- Do not install software from untrusted sources.
- Do not open websites or follow links from untrusted sources.
WAGO has published a security advisory that can be viewed here:
https://www.wago.com/medias/SA-WBM-2018-004.pdf
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.