All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 6.3
- ATTENTION: Exploitable remotely/low skill level to exploit.
- Vendor: Advantech
- Equipment: Advantech WebAccess HMI Designer
- Vulnerabilities: Heap-based Buffer Overflow, Double Free, Out-of-bounds Write
2. RISK EVALUATION
Successful exploitation of these vulnerabilities may allow an attacker to remotely execute arbitrary code.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following version of Advantech WebAccess HMI Designer, a Human Machine Interface (HMI) Runtime Development Software, is affected:
- Advantech WebAccess HMI Designer, Version 2.1.7.32 and prior.
3.2 VULNERABILITY OVERVIEW
3.2.1 HEAP-BASED BUFFER OVERFLOW CWE-122
Heap-based buffer overflow vulnerabilities caused by processing specially crafted .pm3 files may allow remote code execution.
CVE-2018-8833 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).
3.2.2 DOUBLE FREE CWE-415
Double free vulnerabilities caused by processing specially crafted .pm3 files may allow remote code execution.
CVE-2018-8835 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).
3.2.3 OUT-OF-BOUNDS WRITE CWE-787
Processing specially crafted .pm3 files may cause the system to write outside the intended buffer area and may allow remote code execution.
CVE-2018-8837 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).
3.3 BACKGROUND
- Critical Infrastructure Sectors: Critical Manufacturing, Energy, Water and Wastewater Systems
- Countries/Areas Deployed: East Asia, United States, Europe
- Company Headquarters Location: Taiwan
3.4 RESEARCHER
Steven Seeley of Source Incite working with Trend Micro’s Zero Day Initiative (ZDI) reported these vulnerabilities to NCCIC.
4. MITIGATIONS
NCCIC is working with Advantech to provide mitigation steps to resolve the issues that have been reported in Advantech’s WebAccess HMI Designer.
NCCIC recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.