Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
1. EXECUTIVE SUMMARY
- CVSS v3 5.3
- ATTENTION: Exploitable remotely.
- Vendor: Acoustic Technology, Inc. (ATI Systems)
- Equipment: ATI Emergency Mass Notification Systems
- Vulnerabilities: Improper Authentication, Missing Encryption of Sensitive Data.
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could trigger false alarms.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following ATI’s Emergency Mass Notification Systems devices are affected:
- HPSS16
- HPSS32
- MHPSS, and
- ALERT4000.
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER AUTHENTICATION CWE-287
Improper authentication vulnerability caused by specially crafted malicious radio transmissions may allow an attacker to remotely trigger false alarms.
CVE-2018-8862 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).
3.2.2 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311
Missing encryption of sensitive data vulnerability caused by specially crafted malicious radio transmissions may allow an attacker to remotely trigger false alarms.
CVE-2018-8864 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).
3.3 BACKGROUND
- Critical Infrastructure Sectors: Commercial Facilities, Defense Industrial Base, Emergency Services, Government Facilities, Nuclear Reactors, Materials, and Waste
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Massachusetts
3.4 RESEARCHER
Balint Seeber of Bastille reported these vulnerabilities to NCCIC.
4. MITIGATIONS
ATI has created a patch which adds additional security features to the command packets sent over the radio. ATI is testing this patch, and it will be available upon request. Many systems are engineered to meet specific user needs and users need to make sure any upgrades are appropriate for their systems.
ATI recommends that, where feasible, simple voice radios be replaced with digital P-25 (APCO) radios, which provide highly secure encrypted links.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities. High skill level is needed to exploit.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.