Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CVSS v3 9.8
ATTENTION: Remotely exploitable/low skill level to exploit.
Vendor: Moxa
Equipment: OnCell G3100-HSPA Series
Vulnerabilities: Reliance on Cookies without Validation and Integrity Checking, Improper Handling of Length Parameter Inconsistency, NULL Pointer Dereference
AFFECTED PRODUCTS
The following versions of OnCell, a high-speed industrial-grade IP gateway, are affected:
- OnCell G3100-HSPA Series version 1.4 Build 16062919 and prior.
IMPACT
Successful exploitation of these vulnerabilities may allow an attacker to remotely execute code on the device.
MITIGATION
Moxa has released new firmware for OnCell G3100-HSPA that is available via the following link:
https://www.moxa.com/support/download.aspx?type=support&id=13668
NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
VULNERABILITY OVERVIEW
The application allows a cookie parameter to consist of only digits, allowing an attacker to perform a brute force attack bypassing authentication and gaining access to device functions.
CVE-2018-5455 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
An attacker may be able to edit the element of an HTTP request, causing the device to become unavailable.
CVE-2018-5453 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
The application does not check for a NULL value, allowing for an attacker to perform a denial of service attack.
CVE-2018-5449 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
RESEARCHER
Kirill Nesterov, Eugenie Potseluevskaya, and Radu Motspan of Kaspersky Labs reported the vulnerabilities to NCCIC.
BACKGROUND
Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, Transportation Systems
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Taiwan
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.