Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CVSS v3 9.8
ATTENTION: Remotely exploitable/low skill level to exploit.
Vendor: Siemens
Equipment: SIMATIC WinCC Add-On
Vulnerabilities: Stack-based Buffer Overflow, Improper Input Validation, Improper Restriction of Operations within the Bounds of a Memory Buffer, Security Features, Improper Access Control.
UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled ICSA-18-018-01 Siemens SIMATIC WinCC Add-On that was published January 18, 2018, on the NCCIC/ICS-CERT website.
AFFECTED PRODUCTS
Siemens reports that the vulnerabilities affect the following versions of SIMATIC WinCC Add-On:
- SIMATIC WinCC Add-On Historian CONNECT ALARM all versions prior to and including v5.x,
- SIMATIC WinCC Add-On PI CONNECT ALARM all versions prior to and including v2.x,
- SIMATIC WinCC Add-On PI CONNECT AUDIT TRAIL all versions prior to and including v1.x,
- SIMATIC WinCC Add-On PM-AGENT all versions prior to and including v5.x,
- SIMATIC WinCC Add-On PM-ANALYZE all versions prior to and including v7.x,
- SIMATIC WinCC Add-On PM-CONTROL all versions prior to and including v10.x,
- SIMATIC WinCC Add-On PM-MAINT all versions prior to and including v9.x,
- SIMATIC WinCC Add-On PM-OPEN EXPORT all versions prior to and including v7.x,
- SIMATIC WinCC Add-On PM-OPEN HOST-S all versions prior to and including v7.x,
- SIMATIC WinCC Add-On PM-OPEN IMPORT all versions prior to and including v6.x,
- SIMATIC WinCC Add-On PM-OPEN PI all versions prior to and including v7.x,
- SIMATIC WinCC Add-On PM-OPEN PV02 all versions prior to and including v1.x,
- SIMATIC WinCC Add-On PM-OPEN TCP/IP all versions prior to and including v8.x,
- SIMATIC WinCC Add-On PM-QUALITY all versions prior to and including v9.x,
- SIMATIC WinCC Add-On SICEMENT IT MIS all versions prior to and including v7.x, and
- SIMATIC WinCC Add-On SIPAPER IT MIS all versions prior to and including v7.x
IMPACT
Successful exploitation of these vulnerabilities could allow remote code execution or a denial of service condition.
MITIGATION
Gemalto has released an updated installer and Siemens strongly encourages users upgrade to the new installer as soon as possible. The new installer is available at:
https://supportportal.gemalto.com/csm/?id=kb_article&sys_id=a459d328dba207c8fe0aff3dbf9619ce
Siemens also advises that users configure the operational environment according to Siemens’ Operational Guidelines for Industrial Security:
https://www.siemens.com/cert/operational-guidelines-industrial-security
For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-127490 at the following location:
http://www.siemens.com/cert/advisories
NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
VULNERABILITY OVERVIEW
Malformed ASN1 streams in V2C and similar input files can be used to generate stack-based buffer overflows. The vulnerability could allow arbitrary code execution.
CVE-2017-11496 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
Language packs containing malformed filenames could lead to a stack-based buffer overflow. The vulnerability could allow arbitrary code execution.
CVE-2017-11497 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
Language pack (ZIP file) with invalid HTML files could lead to NULL pointer access. The vulnerability could cause denial of service of the remote process.
CVE-2017-11498 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
--------- Begin Update A Part 1 of 1 --------
A stack overflow flaw in the custom XML parser could allow remote denial of service.
CVE-2017-12818 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
Remote manipulation of the language pack updater could allow NTLM relay attacks.
CVE-2017-12819 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
Arbitrary memory read from controlled memory pointer could allow remote denial of service.
CVE-2017-12820 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A memory corruption flaw could allow remote code execution.
CVE-2017-12821 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
The administrative interface can be remotely enabled and disabled without authentication. This could increase the attack surface.
CVE-2017-12822 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).
--------- End Update A Part 1 of 1 ----------
RESEARCHER
Sergey Temnikov and Vladimir Dashchenko from Kaspersky Lab reported these vulnerabilities to Siemens.
BACKGROUND
Critical Infrastructure Sectors: Chemical, Energy, Food and Agriculture, Water and Wastewater Systems.
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Germany
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.