All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CVSS v3 4.3
ATTENTION: Low skill level to exploit.
Vendor: Siemens
Equipment: 7KM PAC Switched Ethernet
Vulnerability: Resource Exhaustion
AFFECTED PRODUCTS
Siemens reports that the vulnerability affects the following 7KM PAC Switched Ethernet PROFINET expansion modules:
- 7KM PAC Switched Ethernet PROFINET expansion module: All versions prior to V2.1.3
IMPACT
Successful exploitation of this vulnerability could cause a denial-of-service condition in the affected component that may require a manual restart of the main device to recover.
MITIGATION
Siemens provides firmware Version V2.1.3 for 7KM PAC Switched Ethernet PROFINET expansion modules, which fixes the vulnerability, and recommends users to update to the new fixed version. The new firmware update can be found at the following location:
https://support.industry.siemens.com/cs/ww/en/view/109749555
Siemens recommends users protect network access with appropriate mechanisms such as firewalls, segmentation, and VPNs. Siemens also advises that users configure the operational environment according to Siemens’ Operational Guidelines for Industrial Security:
https://www.siemens.com/cert/operational-guidelines-industrial-security
For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security Advisory SSA-771218 at the following location:
http://www.siemens.com/cert/advisories
NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not remotely exploitable.
VULNERABILITY OVERVIEW
A denial-of-service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover.
CVE-2017-9945 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
RESEARCHER
Siemens reported this vulnerability and released an advisory with firmware update information.
BACKGROUND
Critical Infrastructure Sectors: Energy
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Germany
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.