All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CVSS v3 8.8
ATTENTION: Remotely Exploitable/low skill level to exploit
Vendor: Schneider Electric
Equipment: Wonderware InTouch Access Anywhere
Vulnerabilities: Cross-Site Request Forgery, Information Exposure, Inadequate Encryption Strength
AFFECTED PRODUCTS
The following Wonderware InTouch Access Anywhere versions are affected:
- Wonderware InTouch Access Anywhere, version 11.5.2 and prior.
IMPACT
Successful exploitation of these vulnerabilities could allow an attacker to perform actions on behalf of a legitimate user, perform network reconnaissance, and gain access to resources beyond those intended with normal operation of the product.
MITIGATION
Schneider Electric has released a new software version to address the identified vulnerabilities and recommends that users of affected versions upgrade to Wonderware InTouch Access Anywhere 2017 (17.0.0).
Users of Wonderware InTouch Access Anywhere can login at the following support site to download the upgrade:
https://gcsresource.invensys.com/tracking/ConfirmDownload.aspx?id=22401
Schneider Electric has issued Security Bulletin LFSEC00000114, which contains additional information:
http://software.schneider-electric.com/support/cyber-security-updates/
NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
VULNERABILITY OVERVIEW
The client request may be forged from a different site. This will allow an external site to access internal RDP systems on behalf of the currently logged in user.
CVE-2017-5156 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
Credentials may be exposed to external systems via specific URL parameters, as arbitrary destination addresses may be specified.
CVE-2017-5158 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated by Schneider Electric; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
The software will connect via Transport Layer Security without verifying the peer’s SSL certificate properly.
CVE-2017-5160 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:N/A:N).
RESEARCHER
Ruslan Habalov and Jan Bee of the Google ISA Assessments Team identified these vulnerabilities.
BACKGROUND
Critical Infrastructure Sectors: Critical Manufacturing, Energy, Healthcare and Public Health, and Water and Wastewater Systems
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Paris, France
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.