All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Independent researcher Maxim Rupp has identified vulnerabilities in Honeywell’s XL Web II controller application. Honeywell has produced a new version to mitigate these vulnerabilities.
These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following XL Web II controller versions are affected:
- XL1000C500 XLWebExe-2-01-00 and prior, and
- XLWeb 500 XLWebExe-1-02-08 and prior.
IMPACT
An attacker may use these vulnerabilities to expose a password by accessing a specific URL. The XL Web II controller application effectively becomes an entry point into the network where it is located.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Honeywell is a US-based company that maintains offices worldwide.
The affected products, XL Web II controllers, are web-based SCADA systems. According to Honeywell, XL Web II controllers are deployed across several sectors including Critical Manufacturing, Energy, Water and Wastewater Systems, and others. Honeywell estimates that these products are used primarily in Europe and the Middle East.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
PLAINTEXT STORAGE OF A PASSWORDa
Any user is able to disclose a password by accessing a specific URL.
CVE-2017-5139b has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).c
INSUFFICENTLY PROTECTED CREDENTIALSd
Password is stored in clear text.
CVE-2017-5140e has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).f
SESSION FIXATIONg
An attacker can establish a new user session, without invalidating any existing session identifier, which gives the opportunity to steal authenticated sessions.
CVE-2017-5141h has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:L/A:L).i
IMPROPER PRIVILEGE MANAGEMENTj
A user with low privileges is able to open and change the parameters by accessing a specific URL.
CVE-2017-5142k has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:L).l
PATH TRAVERSALm
A user without authenticating can make a directory traversal attack by accessing a specific URL.
CVE-2017-5143n has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L).o
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
An attacker with a low skill would be able to exploit these vulnerabilities.
MITIGATION
Honeywell has developed Version 3.04.05.05 to fix the vulnerabilities in the XL Web II controllers. Users are encouraged to contact the local Honeywell HBS branch to have their sites updated to the latest version.
In the Centraline partner channel, Excel Web controllers also have been sold under the brand name “FALCON.” Users can obtain the latest versions by contacting Centraline:
https://www.centraline.com/enGB/centraline/contact.html
ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aCWE-256: Plaintext Storage of a Password, https://cwe.mitre.org/data/definitions/256.html, web site last accessed February 02, 2017.
- bNVD, https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-5139, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- cCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, web site last accessed February 02, 2017.
- dCWE-522: Insufficiently Protected Credentials https://cwe.mitre.org/data/definitions/522.html, web site last accessed February 02, 2017.
- eNVD, https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-5140, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- fCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, web site last accessed February 02, 2017.
- gCWE-384: Session Fixation, https://cwe.mitre.org/data/definitions/384.html, web site last accessed February 02, 2017.
- hNVD, https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-5141, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- iCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:L/A:L, web site last accessed February 02, 2017.
- jCWE-269: Improper Privilege Management, https://cwe.mitre.org/data/definitions/269.html, web site last accessed February 02, 2017.
- kNVD, https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-5142, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- lCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:L, web site last accessed February 02, 2017.
- mCWE-23: Relative Path Traversal, https://cwe.mitre.org/data/definitions/23.html, web site last accessed February 02, 2017.
- nNVD, https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-5143, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- oCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L, web site last accessed February 02, 2017.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report