All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
David Atch of CyberX has identified a buffer overflow vulnerability in Schneider Electric’s Modicon M340 PLC product line. Schneider Electric has produced a new firmware patch to mitigate this vulnerability.
This vulnerability could be exploited remotely.
AFFECTED PRODUCTS
Schneider Electric reports that the vulnerability affects the following Modicon M340 PLC products:
- BMXNOC0401,
- BMXNOE0100,
- BMXNOE0100H,
- BMXNOE0110,
- BMXNOE0110H,
- BMXNOR0200,
- BMXNOR0200H,
- BMXP342020,
- BMXP342020H,
- BMXP342030,
- BMXP3420302,
- BMXP3420302H, and
- BMXPRA0100.
IMPACT
Successful exploitation of this vulnerability could cause the device that the attacker is accessing to crash; a buffer overflow condition may allow remote code execution.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
Schneider Electric is a Europe-based company that maintains offices in 190 countries worldwide.
The affected products, Modicon M340, are PLC devices. According to Schneider Electric, Modicon PLCs are deployed across several sectors including Defense Industrial Base; Energy; Government Facilities; Nuclear Reactors, Materials, and Waste; Transportation Systems; Water and Wastewater Systems; and others. Schneider Electric estimates that these products are used primarily in the United States, China, Russia, and India.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
STACK-BASED BUFFER OVERFLOWa
The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution.
CVE-2015-7937b has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).c
VULNERABILITY DETAILS
EXPLOITABILITY
This vulnerability could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target this vulnerability.
DIFFICULTY
An attacker with a low skill would be able to exploit this vulnerability.
MITIGATION
Schneider Electric produced a new firmware patch to mitigate this vulnerability.
Schneider Electric recommends this workaround:
- Block Port 80 using a firewall.
Schneider Electric has also published a new firmware publication schedule.
Firmware Release dates:
- BMXNOC0401 December 15, 2015,
- BMXNOE0100 (H) December 15, 2015,
- BMXNOE0110 (H) December 15, 2015,
- BMXNOR0200 (H) January 16, 2016,
- BMXP342020 January 16, 2016,
- BMXP3420302 January 16, 2016, and
- BMXPRA0100 January 16, 2016.
For more information on this vulnerability and detailed instructions, please see SEVD-2015-344-01 at the following location:
http://www.schneider-electric.com/ww/en/download/document/SEVD-2015-344-01
ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aCWE-121:Stack-based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed December 17, 2015.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7937, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- cCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, web site last accessed December 17, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.