All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Independent researcher Aditya K. Sood has identified vulnerabilities in Adcon Telemetry’s A840 Telemetry Gateway Base Station. Adcon Telemetry has stated that the A840 is an obsolete product and is no longer supported. No patches or updates will be created for this product. Adcon Telemetry sent a message to all known customers to offer to upgrade to a more secure and stable version.
These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following Adcon Telemetry product is affected:
- A840 Telemetry Gateway Base Station, all versions.
IMPACT
An attacker can gain administrative access to the target by exploiting these vulnerabilities.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Adcon Telemetry is an Austria-based company that maintains offices in several countries around the world, including the US, Germany, and Austria.
The affected product, A840 Telemetry Gateway Base Station, is a wireless telemetry system. According to Adcon Telemetry, A840 Telemetry Gateway Base Stations are deployed across several sectors including Commercial Facilities, Critical Manufacturing, Water and Wastewater Systems, and others. Adcon Telemetry estimates that this product is used primarily in the United States and Europe.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
HARD-CODED CREDENTIALSa
An attacker can log into the device using the hard-coded credentials that grant administrative access. Administrative credentials allow users to change device settings and read and write to the file system. This could result in a loss of confidentiality, integrity, or availability.
CVE-2015-7930b has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N).c
IMPROPER AUTHENTICATIONd
System does not support SSL for encrypting network level communication. Because the support is not available in the Java client, the network communication is plaintext, and all data are transmitted in plaintext.
CVE-2015-7931e has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N).f
CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATIONg
Because there is no SSL support, all the communication is unencrypted making it easily readable over the network.
CVE-2015-7932h has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).i
INFORMATION EXPOSUREj
The Java client used in A840 gateway systems reveals the full path of log files on the server.
CVE-2015-7934k has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).l
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
An attacker with a low skill would be able to exploit these vulnerabilities.
MITIGATION
Adcon Telemetry has stated that the A840 is an obsolete product and is no longer supported. No patches or updates will be created for this product. Adcon Telemetry sent a message to all known customers to offer to upgrade to a more secure and stable version.
ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Install equipment behind a firewall that requires VPN access.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scamsm for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacksn for more information on social engineering attacks.
- a. CWE-798:Use of Hard-coded Credentials, http://cwe.mitre.org/data/definitions/798.html, web site last accessed December 15, 2015.
- b. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7930, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- c. CVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N, web site last accessed December 15, 2015.
- d. CWE-287: Improper Authentication, http://cwe.mitre.org/data/definitions/287.html, web site last accessed December 15, 2015.
- e. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7931, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- f. CVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:N, web site last accessed December 15, 2015.
- g. CWE-319:Cleartext Transmission of sensitive Information, http://cwe.mitre.org/data/definitions/319.html, web site last accessed December 15, 2015.
- h. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7932, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- i. CVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N, web site last accessed December 15, 2015.
- j. CWE-200:Information Exposure, http://cwe.mitre.org/data/definitions/200.html, web site last accessed December 15, 2015.
- k. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7934, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- l. CVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N, web site last accessed December 15, 2015.
- m. Recognizing and Avoiding Email Scams, http://www.us-cert.gov/reading_room/emailscams_0905.pdf, web site last accessed December 15, 2015.
- n. National Cyber Alert System Cyber Security Tip ST04-014, http://www.us-cert.gov/cas/tips/ST04-014.html, web site last accessed December 15, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.