All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Ivan Sanchez from Nullcode Team has identified a DLL Hijacking vulnerability in Open Automation Software’s OPC Systems.NET application. Open Automation Software has reviewed the vulnerability and determined not to patch the issue at this time.
This vulnerability could be exploited remotely with social engineering.
AFFECTED PRODUCTS
The following OPC Systems.NET versions are affected:
- OPC Systems.NET Version 8.00.0023 and previous versions.
IMPACT
Exploitation of DLL Hijack vulnerabilities gives an attacker access to the system with the same privilege level as the application that utilizes the malicious DLL.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
Open Automation Software is a US-based company with offices around the world.
The affected product, OPC Systems.NET, is a NET product for supervisory control and data acquisition (SCADA) and human-machine interface (HMI) applications.
According to Open Automation Software, OPC Systems.NET is an HMI application that is deployed across several sectors including Critical Manufacturing, Energy, Water and Wastewater Systems, and others. Open Automation Software estimates that these products are used throughout the world with primary use in the United States.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
UNCONTROLLED SEARCH PATH ELEMENTa
A successful exploit of this vulnerability requires the local user to install a crafted DLL on the victim machine. The application loads the DLL and gives the attacker access at the same privilege level as the application.
CVE-2015-7917b has been assigned to this vulnerability. A CVSS v3 base score of 7.2 and a temporal score of 6.5 have been assigned; the CVSS vector string is (AV:L/AC:H/PR:H/UI:R/S:C/C:H/I:H/A:H/E:P/RL:U/RC:R).c
VULNERABILITY DETAILS
EXPLOITABILITY
This vulnerability is not exploitable remotely and cannot be exploited without user interaction. The exploit is only triggered when a local user runs the vulnerable application and loads the malformed DLL file.
EXISTENCE OF EXPLOIT
No known public exploits specifically target this vulnerability.
DIFFICULTY
Crafting a working exploit for this vulnerability would be difficult. Social engineering is required to convince the user to accept the malformed DLL file. Additional user interaction is needed to load the malformed file. This decreases the likelihood of a successful exploit.
MITIGATION
Open Automation Software has passed the researcher information to its support team to assist customers in the event that they encounter this vulnerability. Users who believe their Open Automation Software OPC Systems.NET is compromised or not functioning correctly should contact Open Automation Software at:
Open Automation Software
support@opcsystems.com
1-800-533-4994
ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
- Additional information on phishing attacks can be found in Alert TA15-213A Recent Email Phishing Campaigns--Mitigation and Response Recommendations available at: https://www.us-cert.gov/ncas/alerts/TA15-213A.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scamsd for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attackse for more information on social engineering attacks.
- aCWE-427: Uncontrolled Search Path Element, http://cwe.mitre.org/data/definitions/427.html, web site last accessed December 10, 2015.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-7917, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- cCVSS Calculator, https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:H/UI:R/S:C/C:H/I:H/A:H/E:P/RL:U/RC:R, web site last accessed December 10, 2015.
- dRecognizing and Avoiding Email Scams, http://www.us-cert.gov/reading_room/emailscams_0905.pdf, web site last accessed December 10, 2015.
- eNational Cyber Alert System Cyber Security Tip ST04-014, http://www.us-cert.gov/cas/tips/ST04-014.html, web site last accessed December 10, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report