ICS Advisory (ICSA-15-253-01)

Yokogawa Multiple Products Buffer Overflow Vulnerabilities

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

OVERVIEW

Yokogawa Electric Corporation has notified NCCIC/ICS-CERT of stack-based buffer overflow vulnerabilities in multiple Yokogawa products. Yokogawa has released product revisions that mitigate the vulnerabilities for many of the vulnerable products.

These vulnerabilities could be exploited remotely.

AFFECTED PRODUCTS

The following Yokogawa products are affected:

  • CENTUM series:
    • CENTUM CS 1000 (R3.08.70 or earlier),
    • CENTUM CS 3000 (R3.09.50 or earlier),
    • CENTUM CS 3000 Entry (R3.09.50 or earlier),
    • CENTUM VP (R5.04.20 or earlier),
    • CENTUM VP Entry (R5.04.20 or earlier),
  • ProSafe-RS (R3.02.10 or earlier),
  • Exaopc (R3.72.00 or earlier),
  • Exaquantum (R2.85.00 or earlier),
  • Exaquantum/Batch (R2.50.30 or earlier),
  • Exapilot (R3.96.10 or earlier),
  • Exaplog (R3.40.00 or earlier),
  • Exasmoc (R4.03.20 or earlier),
  • Exarqe (R4.03.20 or earlier),
  • Field Wireless Device OPC Server (R2.01.02 or earlier),
  • PRM (R3.12.00 or earlier),
  • STARDOM VDS (R7.30.01 or earlier),
  • STARDOM OPC Server for Windows (R3.40 or earlier),
  • FAST/TOOLS (R10.01 or earlier),
  • B/M9000CS (R5.05.01 or earlier),
  • B/M9000 VP (R7.03.04 or earlier), and
  • FieldMate (R1.01 or R1.02).

IMPACT

Successful exploitation of these vulnerabilities could result in a denial-of-service condition impacting network communications and allow arbitrary code execution.

Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.

BACKGROUND

Yokogawa is based in Japan and maintains offices in several countries around the world, including the Americas, Europe, the Middle East, Africa, South Asia, and East Asia.

The condensed descriptions of the affected products are provided as a quick reference.

  • The CENTUM series products are Windows-based control systems. According to Yokogawa, these products are deployed across several sectors, including Critical Manufacturing, Energy, Food and Agriculture, and others.
  • ProSafe-RS is an integrated distributed control system and safety instrumented system PLC for process industries.
  • Exaopc is an interface package that is OPC compliant.
  • Exaquantum is a plant information management system.
  • Exapilot is an online navigation tool that guides operators through plant operating procedures.
  • Exaplog is an event analysis package.
  • Exasmoc is a multivariable model predictive controller. This controller is widely used in oil and petrochemical plants.
  • Exarqe is a software package that provides product quality information. This controller is widely used in oil and petrochemical plants.
  • Field Wireless Device OPC Server provides field wireless gateway data to the OPC client via an OPC interface.
  • PRM is a plant asset management software tool.
  • STARDOM VDS stands for Versatile Data Server software, which is web-based HMI and SCADA software.
  • STARDOM is a network-based control system.
  • FAST/TOOLS is a software package that implements a web-based supervisory control HMI.
  • B/M9000CS and B/M9000 VP are quality control systems.
  • FieldMate is a device management tool.

Yokogawa estimates that its products are used worldwide.

VULNERABILITY CHARACTERIZATION

VULNERABILITY OVERVIEW

STACK-BASED BUFFER OVERFLOWa

A specially crafted packet transmitted to the process that executes control over network communications can cause network communications to become unresponsive.

CVE-2015-5626b has been assigned to this vulnerability. Yokogawa has assigned a CVSS v2 base score of 10.0; the CVSS vector string is (AV:N/AC:L/Au:N/C:C/I:C/A:C).c

STACK-BASED BUFFER OVERFLOWd

A specially crafted packet is transmitted to the process that executes control over network communications can cause the process that uses the communication function to become unavailable.

CVE-2015-5627e has been assigned to this vulnerability. Yokogawa has assigned a CVSS v2 base score of 10.0; the CVSS vector string is (AV:N/AC:L/Au:N/C:C/I:C/A:C).f

STACK-BASED BUFFER OVERFLOWg

A specially crafted packet transmitted to the process that executes control over network communication may allow a remote attackers to execute arbitrary code.

CVE-2015-5628h has been assigned to this vulnerability. Yokogawa has assigned a CVSS v2 base score of 10.0; the CVSS vector string is (AV:N/AC:L/Au:N/C:C/I:C/A:C).i

VULNERABILITY DETAILS

EXPLOITABILITY

These vulnerabilities could be exploited remotely.

EXISTENCE OF EXPLOIT

No known public exploits specifically target these vulnerabilities.

DIFFICULTY

An attacker with low skill would be able to exploit these vulnerabilities.

MITIGATION

Yokogawa has released product revisions for multiple affected products that remediate the identified vulnerabilities. Yokogawa’s Security Advisory Report, YSAR-15-0003 Vulnerabilities of Communication Functions in CENTUM, and other YOKOGAWA products are available at the following URL:

http://www.yokogawa.com/dcs/security/ysar/dcs-ysar-index-en.htm

For additional information about the vulnerabilities and to obtain Yokogawa’s product revisions, contact Yokogawa via its Security web site at:

https://plus.yokogawa.co.jp/gw/gw.po?c-id=000498

Yokogawa offers the following recommendations to minimize the risk associated with these vulnerabilities by applying the actions:

Apply properly configured firewall between the external network and control system network to prevent external communication with the affected devices.
Prevent unapproved devices from being connected to the network where vulnerable products are connected.

ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.

  • aCWE-121: Stack-based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed September 10, 2015.
  • bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-5626, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
  • cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, web site last accessed September 10, 2015.
  • dCWE-121: Stack-based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed September 10, 2015.
  • eNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-5627, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
  • fCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, web site last accessed September 10, 2015.
  • gCWE-121: Stack-based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed September 10, 2015.
  • hNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-5628, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
  • iCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, web site last accessed September 10, 2015.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report