All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Schneider Electric has notified NCCIS/ICS-CERT of a buffer overflow vulnerability in the Schneider Electric VAMPSET software product. Ricardo Narvaja and Joaquín Rodríguez of Core Security reported this vulnerability directly to Schneider Electric. Schneider Electric has published a security notification,a which tells how to mitigate this vulnerability.
AFFECTED PRODUCTS
Schneider Electric reports that the vulnerability affects the following versions of VAMPSET:
- VAMPSET software, V2.2.145 and all previous versions.
IMPACT
An attacker who exploits this vulnerability may be able to execute arbitrary code.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
Schneider Electric’s corporate headquarters is located in Paris, France, and it maintains offices in more than 100 countries worldwide.
The affected product, VAMPSET software, is used to configure and maintain multiple protection relays and arc monitoring units. According to Schneider Electric, this product is deployed in the Energy sector. Schneider Electric estimates that this product is used on all continents and in 60 countries world-wide.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
STACK-BASED BUFFER OVERFLOWb
VAMPSET is vulnerable to a Stack-based and Heap-based buffer overflow attack, which can be exploited by attackers to execute arbitrary code by providing a malicious CFG or DAT file with specific parameters. These malformed or corrupted disturbance recording files cause VAMPSET to crash when opened in a stand-alone state, without connection to a protection relay. This vulnerability has no effect on the Windows Operating System.
CVE-2014-8390c has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 6.6; the CVSS vector string is (AV:L/AC:M/Au:N/C:P/I:C/A:C).d
VULNERABILITY DETAILS
EXPLOITABILITY
This vulnerability is not exploitable remotely and cannot be exploited without user interaction. The exploit is only triggered when a local user runs the vulnerable application and loads the malformed disturbance recording file.
EXISTENCE OF EXPLOIT
No known public exploits specifically target this vulnerability.
DIFFICULTY
Crafting a working exploit for this vulnerability would be difficult. Social engineering is required to convince the user to accept the malformed disturbance recording file. Additional user interaction is needed to load the malformed file, which decreases the likelihood of a successful exploit.
MITIGATION
To protect the computer and configuration files from unauthorized escalation of privileges through manipulation, Schneider Electric recommends users employ best IT practices to secure their computers and relay configuration files. Use of User Access Control (UAC) can further improve the security of the computer. To minimize the risk of attack, users who are not directly using this software on a regular basis are strongly encouraged to delete this application from their computer to reduce the likelihood of attack and to store relay configuration files in a protected location.
Schneider Electric has updated the VAMPSET tool in order to recognize malformed disturbance recorder files. It now checks the length of the text string in the Comtrade file in order to recognize them as being acceptable. This means that the station name and device identification must be the proper length. If these conditions are not met, the software will block opening the file, remain operational, and report to the user that the file is not complete or contains wrong data.
For more information about this issue, see Schneider Electric security notification SEVD-2015-084-01 at the following location on their website:
ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages
- Refer to Recognizing and Avoiding Email Scamse for more information
- Refer to Avoiding Social Engineering and Phishing Attacksf for more information.
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, which is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aSEVD-2015-084-01, http://www2.schneider-electric.com/sites/corporate/en/support/cybersecurity/cyber-security-vulnerabilities-sorted.page, web site last accessed April 02, 2015.
- b . CWE-121: Stack-based Buffer Overflow, http://cwe.mitre.org/data/definitions/121.html, web site last accessed April 02, 2015.
- cNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-8390, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- dCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:M/Au:N/C:P/I:C/A:C, web site last accessed April 02, 2015.
- eRecognizing and Avoiding Email Scams, http://www.us-cert.gov/reading_room/emailscams_0905.pdf, web site last accessed April 02, 2015.
- fNational Cyber Alert System Cyber Security Tip ST04-014, http://www.us-cert.gov/cas/tips/ST04-014.html, web site last accessed April 02, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.