Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
This updated advisory is a follow-up to the original advisory titled ICSA-15-085-01 Schneider Electric InduSoft Web Studio and InTouch Machine Edition 2014 Vulnerabilities, that was published March 26, 2015, to the NCCIC/ICS-CERT web site.
Gleb Gritsai, Ilya Karpov, and Kirill Nesterov of Positive Technologies Security Lab and independent researcher Alisa Esage Shevchenko have identified vulnerabilities in the Schneider Electric InduSoft Web Studio and InTouch Machine Edition 2014. Schneider Electric has released new patches that mitigate these vulnerabilities.
Public exploits that target these vulnerabilities may exist.
AFFECTED PRODUCTS
The following Schneider Electric products are affected:
- InduSoft Web Studio, Version 7.1.3.2 and all previous versions and
- InTouch Machine Edition 2014, version 7.1.3.2 and all previous versions.
IMPACT
An attacker who exploits these vulnerabilities may be able to execute arbitrary code.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Schneider Electric’s corporate headquarters is located in Paris, France, and maintains offices in more than 100 countries worldwide.
The affected products, Schneider Electric Wonderware InTouch Machine Edition and Schneider Electric InduSoft Web Studio, are embedded HMI software packages. According to Schneider Electric, these products are used in energy management operations in the Commercial Facilities, Energy, Food and Agriculture, and Information Technology sectors globally.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
USE OF HARD-CODED CREDENTIALSa
Sensitive information is stored in Project Files and Project Configuration Files. This information is protected using a hard-coded, clear text password.
CVE-2015-0996b has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 4.7; the CVSS vector string is (AV:L/AC:M/Au:N/C:C/I:N/A:N).c
AUTHENTICATIONd
When connecting to server from HMI, available user names are presented to the screen allowing for potential brute force attacks.
CVE-2015-0997e has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 3.3; the CVSS vector string is (AV:A/AC:L/Au:N/C:P/I:N/A:N).f
CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATIONg
User credentials are sent in clear text allowing for malicious actors to access the control system.
CVE-2015-0998h has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 3.3; the CVSS vector string is (AV:A/AC:L/Au:N/C:P/I:N/A:N).i
CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATIONj
OPC User Credentials are stored in a configuration file in cleartext.
CVE-2015-0999k has been assigned to this vulnerability. Schneider Electric has assigned a CVSS v2 base score of 5.2; the CVSS vector string is (AV:L/AC:L/Au:S/C:C/I:P/A:N).l
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited from an adjacent network.
EXISTENCE OF EXPLOIT
Public exploits that target these vulnerabilities may exist.
DIFFICULTY
An attacker with a low skill would be able to exploit these vulnerabilities.
MITIGATION
Schneider Electric has two divisions supporting this product under separate organizations. Patch availability and technical information is available at these separate divisional support units. Schneider Electric has issued separate security notices for each specific division/product support center.
SEVD-2015-054-01 - InduSoft Web Studio
Schneider Electric has released patches, available for download, to remediate the noted vulnerabilities.
The patch for InduSoft Web Studio, Version 7.1.3.4, Service Pack 3, Patch 4, is available for download using this URL:
http://www.indusoft.com/dev/INDUSOFT/Release/IWS71.3.4/IWS71.3.4.zip
SEVD-2015-054-02 - InTouch Machine Edition 2014
This document is intended to help provide an overview of the identified vulnerability and actions required to mitigate it. To obtain full details on the issues and assistance on how to protect your installation, please contact your local Schneider Electric representative. These organizations will be fully aware of the situation and can support you through the process.
For further information on vulnerabilities in Schneider Electric’s products, please visit Schneider Electric’s cybersecurity web page at:
http://www2.schneider-electric.com/sites/corporate/en/support/cybersecurity/cybersecurity.page
--------- Begin Update A Part 1 of 1 --------
Wonderware Security Bulletin LFSEC00000108 - InTouch Machine Edition Security Vulnerability
This document is intended to provide an overview of the identified vulnerability and actions required to mitigate it. To obtain full details on the issues and assistance on how to protect your installation, please contact your Wonderware Global Custom Support representative. These organizations will be fully aware of the situation and can support you through the process.
https://gcsresource.invensys.com/support/docs/_securitybulletins/Security_bulletin_LFSEC00000108.pdf
For further information on vulnerabilities in Wonderware’s products, please visit Global Customer Support’s Security Central web page at:
https://softwaresupportsp.invensys.com/Pages/securitycentral.aspx
--------- End Update A Part 1 of 1 ----------
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aCWE-798: Use of Hard-coded Credentials, http://cwe.mitre.org/data/definitions/798.html, web site last accessed March 26, 2015.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0996, web site last accessed March 31, 2015.
- cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:M/Au:N/C:C/I:N/A:N, web site last accessed March 26, 2015.
- dCWE-287: Improper Authentication, http://cwe.mitre.org/data/definitions/287.html, web site last accessed March 26, 2015.
- eNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0997, web site last accessed March 31, 2015.
- fCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:A/AC:L/Au:N/C:P/I:N/A:N, web site last accessed March 26, 2015.
- gCWE-319: Cleartext Transmission of Sensitive Information, http://cwe.mitre.org/data/definitions/319.html, web site last accessed March 26, 2015.
- hNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0999, web site last accessed March 31, 2015.
- iCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:A/AC:L/Au:N/C:P/I:N/A:N, web site last accessed March 26, 2015.
- jCWE-319: Cleartext Transmission of Sensitive Information, http://cwe.mitre.org/data/definitions/319.html, web site last accessed March 26, 2015.
- kNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-0999, web site last accessed March 31, 2015.
- lCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:L/Au:S/C:C/I:P/A:N, web site last accessed March 26, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.