All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Siemens has identified a user impersonation vulnerability in its SCALANCE X-200IRT Switch Family. Siemens has produced a firmware update that mitigates this vulnerability.
This vulnerability could be exploited remotely.
AFFECTED PRODUCTS
Siemens reports that the vulnerability affects the following products:
- SCALANCE X-200IRT switch family; All versions prior to V5.2.0
IMPACT
This vulnerability could allow an attacker to impersonate legitimate users of the web interface.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
Siemens is a multinational company headquartered in Munich, Germany.
SCALANCE-X switches are used to connect industrial components like PLCs or HMIs. The switches offer a web interface to enable users to change the configuration using a common web browser, as well as an FTP server to download and upload configuration and firmware files. According to Siemens, these devices are deployed across most sectors including Chemical, Communications, Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agriculture, Government Facilities, Transportation Systems, and Water and Wastewater Systems. Siemens estimates that these products are used worldwide.
VULNERABILITY CHARACTERIZATION
VULNERABILIY OVERVIEW
IMPROPER AUTHENTICATIONa
The device’s web server could allow unauthenticated attackers to impersonate legitimate users of the web interface (Port 80/TCP and Port 443/TCP) if an active web session of an authenticated user exists at the time of attack.
CVE- 2015-1049b has been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).c
VULNERABILITY DETAILS
EXPLOITABILITY
This vulnerability could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target this vulnerability.
DIFFICULTY
An attacker with a medium skill would be able to exploit this vulnerability.
MITIGATION
Siemens provides firmware update V 5.2.0, which fixes the vulnerabilities, and recommends updating as soon as possible. The firmware update is available at:
http://support.automation.siemens.com/WW/view/en/108892137
Siemens strongly recommends protecting network access to the web interface of SCALANCE X‑200IRT switches by appropriate mechanisms. It is advised to follow recommended security practices and to configure the environment according to operational guidelines in order to run the devices in a protected IT environment. Siemens operational guidelines are available at:
For more information on these vulnerabilities and detailed instructions, please see Siemens Security Advisory SSA-954136 at the following location:
http://www.siemens.com/cert/advisories
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aCWE-287: Improper Authentication, http://cwe.mitre.org/data/definitions/287.html, web site last accessed February 03, 2015.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-1049, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed February 03, 2015.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.