Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Researcher Ricardo Narvaja of Core Security Technologies has identified several buffer overflow vulnerabilities in Advantech’s WebAccess application. Advantech has produced a patch that mitigates these vulnerabilities. The researcher has tested the patch to validate that it resolves the vulnerabilities. These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following Advantech WebAccess versions are affected:
- WebAccess Version 7.2.
IMPACT
An attacker may be able to exploit these vulnerabilities to execute arbitrary code on the target machine or crash the WebAccess application.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Advantech is based in Taiwan and has distribution offices in 21 countries worldwide.
Advantech WebAccess, formerly known as BroadWin WebAccess, is a web-based SCADA and human-machine interface product deployed across several sectors including Energy, Critical Manufacturing, Commercial Facilities, and Government Facilities. These systems are deployed globally.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
STACK BUFFER OVERFLOWa
With a specially crafted HTML file that parses the NodeName parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0985bhas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).c
STACK BUFFER OVERFLOWd
With a specially crafted HTML file that parses the GotoCmd parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0986ehas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).f
STACK BUFFER OVERFLOWg
With a specially crafted HTML file that parses the NodeName2 parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0987hhas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).i
STACK BUFFER OVERFLOWj
With a specially crafted HTML file that parses the AccessCode parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0988khas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).l
STACK BUFFER OVERFLOWm
With a specially crafted HTML file that parses the AccessCode2 parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0989nhas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).o
STACK BUFFER OVERFLOWp
With a specially crafted HTML file that parses the UserName parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0990qhas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).r
STACK BUFFER OVERFLOWs
With a specially crafted HTML file that parses the projectname parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0991thas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).u
STACK BUFFER OVERFLOWv
With a specially crafted HTML file that parses the password parameter, an attacker may be able to overflow the stack buffer. The attacker may then be able to remotely execute code on the target device or crash the application.
CVE-2014-0992whas been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).x
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
Crafting a working exploit for this vulnerability would be difficult. Social engineering is required to convince the user to open the malicious HTML file. This file could be located on the local machine or hosted on a web site controlled by the attacker. This decreases the likelihood of a successful exploit.
MITIGATION
Advantech has created a patch (AdvantechWebAccessUSANode_20140730_3.4.3.exe) that mitigates each of the vulnerabilities described above. Users may download the patch from the following location at Advantech’s web site:
For additional information about WebAccess, please visit the following Advantech web site:
http://webaccess.advantech.com/
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scamsyfor more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attackszfor more information on social engineering attacks.
- a. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- b. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0985, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- c. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- d. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- e. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0986, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- f. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- g. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- h. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0987, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- i. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- j. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- k. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0988, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- l. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- m. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- n. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0989, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- o. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- p. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- q. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0990, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- r. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- s. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- t. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0991, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- u. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- v. CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed September 18, 2014.
- w. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0992, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- x. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed September 18, 2014.
- y. Recognizing and Avoiding Email Scams, http://www.us-cert.gov/reading_room/emailscams_0905.pdf, web site last accessed September 18, 2014.
- z. National Cyber Alert System Cyber Security Tip ST04-014, http://www.us-cert.gov/cas/tips/ST04-014.html, web site last accessed September 18, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.