Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
This updated advisory is a follow-up to the updated advisory titled ICSA-14-198-03F Siemens OpenSSL Vulnerabilities that was published October 16, 2014, on the NCCIC/ICS-CERT web site.
--------- Begin Update G Part 1 of 3 --------
Siemens has identified four vulnerabilities in its OpenSSL cryptographic software library affecting several Siemens industrial products. Updates are available for APE 2.0.2, S7-1500, WinCC OA (PVSS), CP1543-1, Ruggedcom ROX 1, and ROX 2-based products.
--------- End Update G Part 1 of 3 ----------
These vulnerabilities could be exploited remotely. Exploits that target OpenSSL vulnerabilities are publicly available. ICS-CERT is unaware of any OpenSSL exploits that target Siemens’ products specifically.
AFFECTED PRODUCTS
The following Siemens products are affected:
--------- Begin Update G Part 2 of 3 --------
- APE (only affected if SSL/TLS component is used):
- APE stand-alone: All versions prior to V2.0.2,
- ELAN on APE: All versions prior to V8.4.0,
- CP1543-1: prior to Version 1.1.25,
- ROX 1: all versions prior to V1.16.1 (only affected if Crossbow is installed),
- ROX 2: all versions prior to V2.6.0 (only affected if ELAN or Crossbow is installed),
- Crossbow: All versions prior to V4.2.3
- ELAN: All versions prior to V8.4.0
- S7-1500: versions prior to Version 1.6, and
- WinCC OA (PVSS): Version 3.12-P001–3.12-P008
--------- End Update G Part 2 of 3 ----------
IMPACT
The vulnerabilities identified could impact authenticity, integrity, and availability of affected devices. The man-in-the-middle attack could allow an attacker to hijack a session between an authorized user and the device. The other vulnerabilities reported could impact the availability of the device by causing the web server of the product to crash.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Siemens is a multinational company headquartered in Munich, Germany. Siemens develops products mainly in the energy, healthcare and public health sectors, and transportation systems.
The affected Siemens industrial products are for process and network control and monitoring in critical infrastructure sectors such as Chemical, Critical Manufacturing, Energy, Food and Agriculture, and Water and Wastewater Systems.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
MAN-IN-THE-MIDDLEa
An attacker could perform a man-in-the-middle (MitM) attack between a vulnerable client and a vulnerable server. This vulnerability affects ROX, APE, S7-1500, and CP1543-1.
CVE-2014-0224b has been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).c
IMPROPER INPUT VALIDATIONd
Specially crafted packets may crash the web server of the product. This vulnerability affects the SIMATIC S7-1500.
CVE-2014-0198e has been assigned to this vulnerability. A CVSS v2 base score of 4.3 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:N/I:N/A:P).f
IMPROPER INPUT VALIDATIONg
Specially crafted packets may crash the web server of the product. This vulnerability affects the SIMATIC S7-1500.
CVE-2010-5298h has been assigned to this vulnerability. A CVSS v2 base score of 4.0 has been assigned; the CVSS vector string is (AV:N/AC:H/Au:N/C:N/I:P/A:P).i
IMPROPER INPUT VALIDATIONj
Specially crafted packets may crash the web server of the product. This vulnerability affects the WinCC OA (PVSS).
CVE-2014-3470k has been assigned to this vulnerability. A CVSS v2 base score of 4.3 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:N/I:N/A:P).l
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
Exploits that target OpenSSL vulnerabilities are publicly available. ICS-CERT is unaware of any OpenSSL exploits that target Siemens’ products specifically.
DIFFICULTY
An attacker with a moderate skill would be able to exploit these vulnerabilities.
MITIGATION
Siemens provides updates for the following products:
--------- Begin Update G Part 3 of 3 --------
APE 2.0.2 stand-alone available at:
http://support.automation.siemens.com/WW/view/en/97654933
S7-1500: update to Version 1.6 at:
http://support.automation.siemens.com/WW/view/de/98164677
WinCC OA (PVSS) available at the Siemens ETM portal.
CP1543-1 update to Version V1.1.25 at:
http://support.automation.siemens.com/WW/view/en/99804563
Updated firmware for Ruggedcom ROX-based devices and ELAN software can be obtained for free from the following contact points:
- Submit a support request to Siemens online:
- Call a local hotline center:
Update Debian using the standard update procedures if eLAN is installed on a Linux system.
--------- End Update G Part 3 of 3 ----------
Siemens provides specific advice for mitigating risk in each of the affected products in SSA‑234763, which can be found at its web site at the following location:
http://www.siemens.com/cert/advisories
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in email messages.
- Refer to Recognizing and Avoiding Email Scamsm for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacksn for more information on social engineering attacks.
- aCWE-310: Cryptographic Issues, http://cwe.mitre.org/data/definitions/310.html, web site last accessed July 17, 2014.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0224, web site last accessed July 17, 2014.
- cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P, web site last accessed July 17, 2014.
- dCWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer, http://cwe.mitre.org/data/definitions/119.html, web site last accessed July 17, 2014.
- eNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0198, web site last accessed July 17, 2014.
- fCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:N/I:N/A:P, web site last accessed July 17, 2014.
- gCWE-362: Concurrent Execution using Shared Resource with Improper Synchronization ('Race Condition'), http://cwe.mitre.org/data/definitions/362.html, web site last accessed July 17, 2014.
- hNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2010-5298, web site last accessed July 17, 2014.
- iCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:H/Au:N/C:N/I:P/A:P, web site last accessed July 17, 2014.
- jCWE-476: NULL Pointer Dereference, http://cwe.mitre.org/data/definitions/476.html, web site last accessed July 17, 2014.
- kNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-3470, web site last accessed July 17, 2014.
- lCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:N/I:N/A:P, web site last accessed July 17, 2014.
- mRecognizing and Avoiding Email Scams, http://www.us-cert.gov/reading_room/emailscams_0905.pdf, web site last accessed July 17, 2014.
- nNational Cyber Alert System Cyber Security Tip ST04-014, http://www.us-cert.gov/cas/tips/ST04-014.html, web site last accessed July 17, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.