All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
This advisory was originally posted to the US-CERT secure Portal library on July 15, 2014, and is being released to the NCCIC/ICS-CERT web site.
Adam Crain of Automatak and Chris Sistrunk of Mandiant have identified a Buffer Overflow Vulnerability in the SUBNET Solutions Inc (SUBNET), SubSTATION Server 2, Telegyr 8979 Master application. SUBNET has produced a hot fix that mitigates this and a related vulnerability the vendor found independently. The researchers have tested the new hot fix and validate that it resolves these vulnerabilities.
These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following SUBNET product is affected:
- SubSTATION Server 2 Telegyr 8979 Master Protocol – All Versions.
IMPACT
By sending specially crafted invalid RTU messages to the Telegyr 8979 master, a buffer overflow can occur, resulting in a denial of service (DoS).
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
SUBNET is based in Calgary, Alberta, Canada.
The affected product, SubSTATION Server, is a vendor agnostic multifunction software application used in intelligent substation automation and IT networking. SubSTATION Server performs data concentration, protocol translation, automation logic, event file collection, and enterprise connectivity. This allows replacement of separate legacy devices, such as RTU data concentrators, relay communications processors used in the operation of electrical substations. According to SUBNET, SubSTATION Server is deployed in the Energy sector including oil and gas and electric utilities. SUBNET estimates that these products are used primarily in the United States and Canada.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
IMPROPER INPUT VALIDATIONa
The researchers found that by sending a specially crafted packet simulating an RTU to Master message exceeding allowable data length, an attacker can cause the Telegyr 8979 Master to crash. SUBNET has also discovered that after sending a specially crafted message containing a valid data length, any subsequent message sent immediately to the Telegyr 8979 will also crash the service. SUBNET had also determined the root issue was in the GPT software library.
CVE-2014-2357b has been assigned to this vulnerability. A CVSS v2 base score of 8.3 has been assigned; the CVSS vector string is (AV:A/AC:L/Au:N/C:C/I:C/A:C).c
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
Crafting a working exploit for these vulnerabilities would be difficult. An attacker with a moderate to high skill level would be able to exploit these vulnerabilities.
MITIGATION
SUBNET has produced hot fix “SSNET v2.12 HF18808” to resolve this issue.
This hot fix can be obtained by secure FTP provided by the SUBNET support department. Please contact SUBNET Customer Support at: (403) 270-8885, or by email at: support@SUBNET.com and reference SUBNET Release Bulletin “SubSTATION Server 2.12 HF18808 Release, 21 May 2014” for a copy of this release bulletin and download/installation information (This bulletin is being sent to registered users only).
Vendor Recommendation:
- The exploit results in an unrecoverable exception, but all software components are registered as Services under Windows and can be configured to automatically restart after any stoppage. Users can configure the service to automatically restart, which limits the DoS to a momentary disruption.
- Backward compatible releases will be available by request for customers using older versions of SubSTATION Server.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- aCWE-20: Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, web site last accessed July 15, 2014.
- bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2357, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?calculator&version=2&vector=AV:A/AC:L/Au:N/C:C/I:C/A:C, web site last accessed July 15, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.