All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
This advisory was originally posted to the US-CERT secure Portal library on June 24, 2014, and is being released to the NCCIC/ICS-CERT web site.
Martin Jartelius of Outpost24 has identified an authentication bypass vulnerability in Honeywell FALCON XLWeb controllers. Juan Francisco Bolivar has identified cross-site scripting vulnerabilities in Honeywell FALCON XLWeb controllers. Honeywell has produced an update that mitigates both vulnerabilities. Mr. Jartelius has tested the update to validate that it resolves the vulnerability that he reported. These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following Honeywell FALCON XLWeb controller versions are affected:
- FALCON Linux 2.04.01 or older
- FALCON XLWebExe 2.02.11 or older.
IMPACT
An attacker may use these vulnerabilities to generate a valid login for an administrative user on the Honeywell FALCON XLWeb controller giving the attacker full administrator access to the system.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
Honeywell is a US-based company that maintains offices worldwide.
The affected products, FALCON XLWeb controllers, are web-based SCADA systems. According to Honeywell, FALCON XLWeb controllers are deployed across several sectors including Critical Manufacturing, Energy, Water and Wastewater Systems, and others. According to Honeywell, the affected controllers are used by customers primarily in Europe and the Middle East.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
FILE ACCESSIBLE TO EXTERNAL PARTIESa
The change password page can be accessed without a valid session or authentication. This page can be used to disclose a user’s password hash or login as a user without knowing the user’s password, making it possible for an attacker to login as an administrative user.
CVE-2014-2717b has been assigned to this vulnerability. A CVSS v2 base score of 7.6 has been assigned; the CVSS vector string is (AV:N/AC:H/Au:N/C:C/I:C/A:C).c
CROSS-SITE SCRIPTINGd
The web server is vulnerable to several cross-site scripting attacks. By sending invalid input through the XL Web controllers, an attacker can execute arbitrary HTML and script code in another user’s browser session.
CVE-2014-3110e has been assigned to this vulnerability. A CVSS v2 base score of 4.3 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:N/A:N).f
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISTENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
An attacker with a moderate skill would be able to exploit these vulnerabilities.
MITIGATION
Honeywell posted a Security Bulletin on Centraline Partnerwebg (login required) that tells how to update FALCON controllers to the latest version.
Honeywell also offers the following advice:
- FALCON controllers (referred to as “XLWeb”) can be found unprotected in the Internet. Because this poses the risk of unauthorized access, immediate action should be taken in order to protect them from unauthorized access.
- All Internet facing FALCON controllers should be operated either in internal networks, or use a coded VPN connection for internet access, in order to limit unauthorized access.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B—Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (www.ics-cert.org).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- a. CWE-552: Files or Directories Accessible to Parties, http://cwe.mitre.org/data/definitions/552.html, web site last accessed July 22, 2014.
- b. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-2717, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- c. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:H/Au:N/C:C/I:C/A:C, web site last accessed July 22, 2014.
- d. CWE-79: Improper Neutralization of Input During Web Page Generation (“Cross-site Scripting”), http://cwe.mitre.org/data/definitions/79.html, web site last accessed July 22, 2014.
- e. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-3110, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
- f. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:N/A:N, web site last accessed July 22, 2014.
- g. Centraline by Honeywell login page, https://www.centraline.com/index.php?id=1, web site last accessed July 22, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.