ICS Advisory (ICSA-14-093-01)

Schneider Electric OPC Factory Server Buffer Overflow

Click to Tweet.
Click to send to Facebook.
Click to Share.

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.


 

OVERVIEW

Researcher Wei Gao, formerly of IXIA, has identified a buffer overflow vulnerability in the Schneider Electric OPC Factory Server (OFS) application. Schneider Electric has produced a patch that mitigates this vulnerability. Wei Gao has tested the patch to validate that it resolves the vulnerability.

This vulnerability could be exploited remotely.

AFFECTED PRODUCTS

Schneider Electric reports that the vulnerability affects the following versions of OFS:

  • TLXCDSUOFS33 – V3.5 and previous,
  • TLXCDSTOFS33 – V3.5 and previous,
  • TLXCDLUOFS33 – V3.5 and previous,
  • TLXCDLTOFS33 – V3.5 and previous, and
  • TLXCDLFOFS33 – V3.5 and previous.

IMPACT

A successful exploitation will cause the server to reboot resulting in a denial of service.

Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.

BACKGROUND

Schneider Electric corporate headquarters is located in Paris, France, and maintains offices in more than 100 countries worldwide.

These products are industrial active energy management control products, deployed across several sectors including the Energy, Water and Wastewater Systems, Commercial Facilities, Government Facilities, Food and Agriculture, and Transportation Systems. Schneider Electric estimates that these products are used primarily in the United States and North America.

VULNERABILITY CHARACTERIZATION

VULNERABILITY OVERVIEW

BUFFER OVERFLOWa

Incorrect parsing in the OPC Automation 2.0 Server Object (ActiveX) can result in a buffer overflow error. The vulnerability is caused by parsing long arguments in functions.

CVE-2014-0789b has been assigned to this vulnerability. A CVSS v2 base score of 5.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:N/I:N/A:P).c

VULNERABILITY DETAILS

EXPLOITABILITY

This vulnerability could be exploited remotely.

EXISTENCE OF EXPLOIT

Exploits that target this vulnerability are publicly available.

DIFFICULTY

An attacker with a low skill would be able to exploit this vulnerability.

MITIGATION

Schneider Electric has developed a patch to resolve this issue. In order to patch the installation in the field, install OFS V3.5SP1, available on Schneider Electric’s web site at the following URL:

http://www.schneider-electric.com/download/WW/EN/results/0/0/8336568-OPC-Factory-Server/0/?showAsIframe=true

OFS V3.5SP1 includes a patched version of the OLE2T macro from Microsoft to resolve the issue.

For more information regarding this issue, please see the security announcements affecting the OPC Factory Server on Schneider Electric’s web site at the following URL:

http://www2.schneider-electric.com/sites/corporate/en/support/cybersecurity/cybersecurity.page

ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.

ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.

  • aCWE-122: Heap-based Buffer Overflow, http://cwe.mitre.org/data/definitions/122.html, web site last accessed April 03, 2014.
  • bNVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0789, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory.
  • cCVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:N/I:N/A:P, web site last accessed April 03, 2014.


Contact Information

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  https://us-cert.cisa.gov/ics 
or incident reporting:  https://us-cert.cisa.gov/report

CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

This product is provided subject to this Notification and this Privacy & Use policy.

Please share your thoughts.

We recently updated our anonymous product survey; we'd welcome your feedback.