All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
NCCIC/ICS-CERT has been following the increase in denial-of-service (DoS) attacks using Network Time Protocol (NTP) Reflection. This type of attack provides an adversary the ability to generate high volume distributed denial of service (DDoS) traffic to target web sites or public‑facing devices that could cause disruption to services.
This vulnerability could be exploited remotely. Exploits that target this type of attack are known to be publicly available.
Mitigations are available for both operators of NTP Stratum devices and possible victims of these attacks.
AFFECTED PRODUCTS
Products using NTP service NTP-4.2.7p25 and prior (with MONLIST support) are affected. No specific vendor is specified as this is an open source protocol.
IMPACT
Exploitation of this vulnerability could cause NTP Stratum devices to be used as sources of unrequested NTP synchronization requests in a DoS attack.
Victims of this type of DoS attack could see service interruption due to boundary protection rules do not filter NTP synchronization requests that do not originate internally.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
BACKGROUND
The NTP is described in RFC 958a, an open source collaboration for acceptance, and is used to synchronize system time over a network.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
IMPROPER INPUT VALIDATIONb
The NTP service could allow for multiple sync requests to be made with a forged source IP address, thus sending the unrequested responses back to the source, consuming its resources. An attacker could exploit this vulnerability by sending a specifically crafted packet with a forged source IP address of the target.
It will not be evident to the NTP operator that the system has been exploited or is being used in a DoS attack as the commands are normal time synchronization requests.
CVE-2013-5211c has been assigned to this vulnerability. A CVSS v2 base score of 7.8 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:N/I:N/A:C).d
VULNERABILITY DETAILS
EXPLOITABILITY
This vulnerability could be exploited remotely.
EXISTENCE OF EXPLOIT
Exploits that target this vulnerability are publicly available.
DIFFICULTY
An attacker with a low skill would be able to exploit this vulnerability.
MITIGATION
NTP can be upgraded to NTP-4.2.7p26 or later that removes MONLIST support and is replaced with the more secure MRUNLIST function. This fix has been available since 2010.
In addition, integrators and asset owners are encouraged to review boundary protection rule sets and filters to eliminate incoming NTP requests that do not originate internally.
NCCIC/US-CERT resource documents that outline suggestions for mitigating active DDoS attacks are available here:
http://www.us-cert.gov/sites/default/files/publications/DDoS%20Quick%20Guide.pdf
http://www.us-cert.gov/ncas/tips/ST04-015
http://www.kb.cert.org/vuls/id/348126
NCCIC/ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
NCCIC/ICS-CERT also provides a section for control systems security recommended practices on the NCCIC/ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. NCCIC/ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the NCCIC/ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B—Targeted Cyber Intrusion Mitigation Strategies, that is available for download from the NCCIC/ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC/ICS-CERT for tracking and correlation against other incidents.
- a. Network Time Protocol (NTP), http://tools.ietf.org/html/rfc958, web site last accessed February 20, 2014.
- b. CWE-20: Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, web site last accessed February 20, 2014.
- c. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2013-5211, NIST uses this advisory to create the CVE web site report. web site last accessed February 20, 2014.
- d. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:N/I:N/A:C, web site last accessed February 20, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.