All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
Researchers Gleb Gritsai, Ilya Karpov, and Kirill Nesterov of Positive Technologies have identified multiple vulnerabilities in the Siemens SIMATIC WinCC Open Architecture (OA) application. Siemens has produced updates that mitigate these vulnerabilities.
These vulnerabilities could be exploited remotely.
AFFECTED PRODUCTS
The following Siemens product is affected:
- SIMATIC WinCC OA all versions prior to 3.12 P002
IMPACT
Successful exploitation of these vulnerabilities may result in attackers escalating their privileges, performing remote code execution, traversing through file systems, or causing a denial of service.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
BACKGROUND
Siemens is a multinational company headquartered in Munich, Germany.
The affected product, SIMATIC WinCC OA, is a client-server human-machine interface (HMI) system. According to Siemens, SIMATIC WinCC OA is deployed across several sectors including food and beverage, water and wastewater, oil and gas, and chemical. Siemens estimates that these products are used primarily in the United States and Europe with a small percentage in Asia.
VULNERABILITY CHARACTERIZATION
VULNERABILITY OVERVIEW
IMPROPER CONTROL OF GENERATION OF CODE (“CODE INJECTION”)a
The SIMATIC WinCC OA integrated Web server at Port 4999/TCP might allow attackers to perform remote code execution by sending specially crafted packets without authentication.
CVE-2014-1697b has been assigned to this vulnerability. A CVSS v2 base score of 9.3 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:C/I:C/A:C).c
RELATIVE PATH TRAVERSALd
The SIMATIC WinCC OA integrated Web server at Port 4999/TCP might allow attackers to traverse through the server’s file system based on the application’s Windows user permissions by sending specially crafted packets over the network without authentication.
CVE-2014-1698e has been assigned to this vulnerability. A CVSS v2 base score of 5.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:N/A:N).f
IMPROPER INPUT VALIDATIONg
The SIMATIC WinCC OA integrated Web server at Port 4999/TCP might allow attackers to perform a denial of service attack on the SIMATIC WinCC OA monitoring service by sending malformed HTTP requests over the network without authentication. Restarting the WinCC OA Console recovers the monitoring service.
CVE-2014-1699h has been assigned to this vulnerability. A CVSS v2 base score of 5.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:N/I:N/A:P).i
USE OF PASSWORD HASH WITH INSUFFICIENT COMPUTATIONAL EFFORTj
The SIMATIC WinCC OA server application has a weak hashing algorithm for project users’ credentials. By brute force, attackers might be able to escalate their privileges within the affected WinCC OA server application.
CVE-2014-1696k has been assigned to this vulnerability. A CVSS v2 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:P/A:P).l
VULNERABILITY DETAILS
EXPLOITABILITY
These vulnerabilities could be exploited remotely.
EXISITENCE OF EXPLOIT
No known public exploits specifically target these vulnerabilities.
DIFFICULTY
An attacker with a low to moderate skill would be able to exploit these vulnerabilities.
MITIGATION
Siemens recommends updating to SIMATIC WinCC OA v3.12 and to install patch P002 January.
SIMATIC WiNCC OA v3.12 can be obtained here (login and password required):
The patch SIMATIC WinCC OA v3.12 P002 January can be obtained here (login and password required):
SIMATIC WinCC OA v3.12 P002 January
Siemens security advisory is located here:
Siemens security advisory SSA-342587
NCCIC/ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
NCCIC/ICS-CERT also provides a section for control systems security recommended practices on the NCCIC/ICS-CERT Web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. NCCIC/ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the NCCIC/ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B—Targeted Cyber Intrusion Mitigation Strategies, that is available for download from the NCCIC/ICS-CERT Web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC/ICS-CERT for tracking and correlation against other incidents.
- a. CWE-94: Improper Control of Generation of Code (“Code Injection”), http://cwe.mitre.org/data/definitions/94.html, Web site last accessed February 4, 2014.
- b. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-1697, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
- c. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:C/I:C/A:C, Web site last visited February 4, 2014.
- d. CWE-23: Relative Path Traversal, http://cwe.mitre.org/data/definitions/23.html, Web site last accessed February 4, 2014.
- e. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-1698, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
- f. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:N/A:N, Web site last visited February 4, 2014.
- g. CWE-20: Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, Web site last accessed February 4, 2014.
- h. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-1699, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
- i. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:N/I:N/A:P, Web site last visited February 4, 2014.
- j. CWE-916: Use of Password Hash With Insufficient Computational Effort, http://cwe.mitre.org/data/definitions/916.html, Web site last accessed February 4, 2014.
- k. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-1696, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
- l. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:P/A:P, Web site last visited February 4, 2014.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.