Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Overview
This advisory was originally posted to the US-CERT secure Portal library on March 08, 2013, and is now being released to the ICS-CERT Web page.
This advisory provides mitigation details for a vulnerability that impacts the Invensys Wonderware Win-XML Exporter.
Researchers Timur Yunusov, Alexey Osipov, and Ilya Karpov of the Positive Technologies Research Team have discovered an improper input validation vulnerability in the Invensys Wonderware Win-XML Exporter. Invensys has released a patch that mitigates the vulnerability. The Positive Technologies Research Team has validated that the patch fixes the vulnerability. Exploitation of this vulnerability could impact systems deployed in the critical manufacturing, energy, food and beverage, chemical, and water and wastewater sectors.
Affected Products
The following Invensys Wonderware products are affected:
- Win-XML Exporter Version 1522, 148, 0, 0, and possibly earlier versions.
Impact
Successful exploitation of this vulnerability could allow an attacker to affect the confidentiality and availability of the Wonderware Win-XML Exporter.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
Background
Invensys is a global technology company that works with industrial, commercial, rail operators, and appliance operators, while operating in over 180 countries. Invensys develops software, systems, and equipment that enable users to monitor, automate, and control their processes.
The Invensys Wonderware Win-XML Exporter is used in many industries worldwide, including critical manufacturing, energy, food and beverage, chemical, and water and wastewater.
The Wonderware Win-XML Exporter converts interface windows from Intouch HMI projects and displays them in Internet Explorer with the help of Wonderware Information Server.
Vulnerability Characterization
Vulnerability Overview
Improper Input Validation1
Wonderware Win-XML Exporter allows access to local resources (files and internal resources) via unsafe parsing of XML external entities. By using specially crafted XML files, an attacker can cause Wonderware Win-XML Exporter to send the contents of local or remote resources to the attacker’s server or cause a denial of service of the system.
CVE-2012-47102 has been assigned to this vulnerability. A CVSS v2 base score of 6.3 has been assigned; the CVSS vector string is (AV:L/AC:M/Au:N/C:C/I:N/A:C).
Vulnerability Details
Exploitability
This vulnerability is not exploitable remotely and cannot be exploited without user interaction. The exploit is only triggered when a local user runs the vulnerable application and loads the malformed XML files.
Existence of Exploit
No known public exploits specifically target this vulnerability.
Difficulty
An attacker with a medium skill would be able to exploit this vulnerability.
Mitigation
Invensys has developed an update to the Win-XML Exporter that mitigates this vulnerability. The Positive Technologies Research Team has tested the update and validated that it fixes the vulnerability. Instructions and a link to the update are found on the Invensys download page.
According to Invensys, any machine running one or more of the products listed above is affected and should be patched. No other components of the Wonderware installed products are affected. Users should install the update using instructions provided in the ReadMe file for the product and component being installed. Invensys recommends that users:
- Read the installation instructions provided with the patch.
- Shut down any of the affected software products.
- Install the update.
- Restart the software.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices. Critical devices should not directly face the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT Web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B—Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- 1. CWE-20 Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, Web site last accessed March 21, 2013.
- 2. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-4710, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.