All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Overview
This advisory provides mitigation details for multiple vulnerabilities that impact the GE Intelligent Platforms Proficy Real-Time Information Portal.
General Electric (GE) has addressed two vulnerabilities in the GE Intelligent Platforms Proficy Real-Time Information Portal. Exploitation of these vulnerabilities would result in information disclosure. The vulnerabilities can be exploited remotely.
GE has produced two security advisories (GEIP12-14 and GEIP12-15) available on the GE Intelligent Platforms support Web site to inform customers about these vulnerabilities.
Affected Products
GE Intelligent Platforms reports that the vulnerabilities affect the following versions:
- Proficy Real-Time Information Portal: All versions.
Impact
CVE-2013-0651 is a security misconfiguration that, if exploited, could allow an unauthenticated remote attacker to retrieve sensitive configuration information such as system usernames and passwords for Portal data sources. The security misconfiguration is a default installation setting that can be subsequently changed.
CVE-2013-0652 is an information disclosure vulnerability that, if exploited, could allow an unauthenticated remote attacker to obtain a list of usernames for users of the Portal application and a limited amount of other technical information that could aid the attacker in conducting additional attacks.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
Background
According to GE, Proficy Real-Time Information Portal is a Web-based data visualization and reporting tool that is deployed across multiple industries worldwide.
Vulnerability Characterization
Vulnerability Overview
Information Disclosure Vulnerability1
By default, the Portal installation creates files and folders in unauthenticated locations on the IIS or Apache Web server. An attacker can exploit this misconfiguration by making an HTTP GET request on Port 80/TCP to retrieve configuration files and other sensitive information.
CVE-2013-0651 has been assigned to this vulnerability. A CVSS v2 base score of 5.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:N/A:N).
Information Disclosure Vulnerability2
Proficy Real-Time Information Portal exposes methods of a vulnerable class via Java RMI. Even with Portal authentication enabled within the application, Portal unnecessarily exposes some of these methods and allows them to be called without authentication. An attacker can exploit the vulnerability by making an RMI call over Port 80/TCP to retrieve information.
CVE-2013-0652 has been assigned to this vulnerability. A CVSS v2 base score of 5.0 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:P/I:N/A:N).
Vulnerability Details
Exploitability
These vulnerabilities could be exploited remotely.
Existence of Exploit
No known public exploits specifically target these vulnerabilities.
Difficulty
An attacker with a low skill would be able to exploit these vulnerabilities.
Mitigation
To mitigate these information disclosure vulnerabilities, GE recommends making the following configuration changes:
- Disable “Anonymous Authentication” and “Windows Authentication.”
- Require authentication for all Portal users.
- Configure an SSL certificate to encrypt Portal application traffic.
Please see GE Intelligent Platforms Product Security Advisory GEIP12-14 and GEIP12-15 for detailed instructions.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
Minimize network exposure for all control system devices. Critical devices should not directly face the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
ICS-CERT also provides a section for control systems security recommended practices on the US-CERT Web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01A—Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.