All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Overview
Arbiter Systems reported to ICS-CERT that a vulnerability that causes a denial of service (DoS) has been identified in Arbiter Systems Power Sentinel Phasor Measurement Unit. The vulnerability can be exploited remotely. Arbiter Systems has produced a patch that mitigates this vulnerability. OSIsoft tested the patch to validate that it resolves the vulnerability.
Affected Products
The following Arbiter Systems Power Sentinel products are affected:
- Model 1133A Power Sentinel, firmware versions 09Jun2012 and earlier.
Impact
Successful exploitation of this vulnerability could lead to a DoS.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of the vulnerability based on their operational environment, architecture, and product implementation.
Background
Arbiter Systems manufactures time clocks, power measurement, and power calibration products for use in electricity generation and transmission. These products are used primarily in the United States. Some are deployed to South America and Europe as well.
Vulnerability Characterization
Vulnerability Overview
Denial of Service1
The Ethernet port on this device stops responding to queries when its buffer is full. Certain types of queries to the Ethernet port, such as port scanning, cause the device to stop responding.
CVE-2012-30122 has been assigned to these vulnerabilities. A CVSS v2 base score of 7.8 has been assigned; the CVSS vector string is (AV:N/AC:L/Au:N/C:N/I:N/A:C).
Vulnerability Details
Exploitability
This vulnerability can be exploited remotely.
Existence of Exploit
No known public exploits specifically target this vulnerability.
Difficulty
An attacker with a low skill would be able to exploit this vulnerability.
Mitigation
Arbiter Systems recommends that users update firmware to 11June2012 Rev 421 or later. This version is available on the product page for Model 1133A at the company Web site (http://www.arbiter.com/news/index.php?id=261). Users will need to download both the firmware as well as the uploader software to send the firmware to the device.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices. Critical devices should not directly face the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
The Control Systems Security Program (CSSP) also provides a section for control systems security recommended practices on the CSSP Web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.3
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper ICS-TIP-12-146-01A—Cyber Intrusion Mitigation Strategies.4
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
- 1CWE-410: Insufficient Resource Pool, http://cwe.mitre.org/data/definitions/410.html, Web site last accessed September 05, 2012.
- 2NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-XXXX, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory.
- 3CSSP Recommended Practices, http://www.us-cert.gov/control_systems/practices/Recommended_Practices.html, Web site last accessed September 05, 2012.
- 4Cyber Intrusion Mitigation Strategies, http://www.us-cert.gov/control_systems/pdf/ICS-TIP-12-146-01A.pdf, Web site last accessed September 05, 2012.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report