All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Overview
ICS-CERT originally released Advisory “ICSA-12-062-01PInvensys Wonderware Information Server Multiple Vulnerabilities” on the US-CERT secure portal on March 02, 2012. This web page release was delayed to allow users time to download and install the update.
Independent security researchers Terry McCorkle and Billy Rios have identified multiple vulnerabilities in the Invensys Wonderware Information Server. Invensys has developed a security update to address these affected products.
Invensys has expressed appreciation to Billy Rios and Terry McCorkle as independent security researchers for the discovery and collaboration with Invensys on resolving these vulnerabilities.
Affected Products
The following Invensys Wonderware Information Server versions are affected:
- 4.0 SP1 and 4.5--Portal
- 4.0 SP1 and 4.5--Client.
The following Invensys Wonderware Historian Client version is affected:
Only Wonderware Historian Client versions installed on the same node as the Wonderware Information Server Portal or Client are subject to the vulnerabilities reported in this Advisory.
Impact
These vulnerabilities, if exploited, could allow denial of service, information disclosure, remote code execution, or session credential high jacking. Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
Background
The Invensys Wonderware Information Server is used in many industries worldwide, including manufacturing, energy, food and beverage, chemical, and water and wastewater.
The Information Server provides industrial information content including process graphics, trends, and reports. The Invensys Wonderware Information Server Web Clients provides access to reports, analysis, or write back capabilities to processes.
Vulnerability Characterization
Vulnerability Overview
Cross-Site Scripting1
This vulnerability enables an attacker to inject client side script into web pages viewed by other users or bypass client side security mechanisms imposed by modern web browsers. This vulnerability, if exploited, could allow arbitrary code execution and may require social engineering to exploit.
CVE-2012-0225 has been assigned to this vulnerability. The Invensys assessment of the compound vulnerabilities using the CVSSd Version 2.0 calculator rates an Overall CVSS Score of 8.1.2
SQL Injection3
This vulnerability can be used by an attacker to perform database operations that were unintended by the web application designer and, in some instances, can lead to total compromise of the database server. This vulnerability, if exploited, could allow arbitrary code execution.
CVE-2012-0226 has been assigned to this vulnerability. The Invensys assessment of the compound vulnerabilities using the CVSSh Version 2.0 calculator rates an Overall CVSS Score of 8.1.4
Permissions, Privileges, and Access Controls5
The security access permissions issues with client controls can lead to denial of service.
CVE-2012-0228 has been assigned to this vulnerability. The Invensys assessment of the compound vulnerabilities using the CVSSk Version 2.0 calculator rates an Overall CVSS Score of 8.1.6
Exploitability
These vulnerabilities are remotely exploitable.
Existence of Exploit
No known exploits specifically target these vulnerabilities.
Difficulty
An attacker with a low skill level can create the denial of service, whereas it would require a more skilled attacker to execute arbitrary code. This attack may require social engineering to exploit.
Mitigation
Invensys has developed software updates to address the reported vulnerabilities. Customers of Invensys running vulnerable versions of Invensys Wonderware Information Server and Invensys Wonderware Historian Client can update their systems to the most recent software updates released by following the steps provided by Invensys.
Invensys software updates can be downloaded from the Wonderware Development Network (“Software Download” area) and the Infusion Technical Support website: https://wdn.wonderware.com/sites/WDN/Pages/Downloads/Software.aspx.
The following steps are provided by Invensys for update information.
Install the Security Update using instructions provided in the ReadMe file for the product and component being installed. In general, the user should proceed as indicated below:
- Wonderware Information Server – Portal component: Run the “Hotfix Install Utility.”
- Wonderware Information Server – Client component: Uninstall the client from Add/Remove Programs (ClientSetup.msi), clear the IE cache (see specific instructions in the Readme file provided with the Security Update) and access the Wonderware Information Server site.
- If Step 2 and Step 3 are on the same node, perform the functions in Step 2 and also run the “Hotfix Install Utility.”
In addition to applying the software updates, Invensys has made additional recommendations to customers running vulnerable versions of the Invensys Wonderware Information Server and Invensys Wonderware Historian Client products. Customers using versions of the products prior to Invensys Wonderware Information Server 5.0 and Invensys Wonderware Historian Client 10 SP3 should apply the security update to all nodes where the Portal and Client components are installed. (All browser clients of the portal are affected and should be patched). Customers using the affected versions of Invensys Wonderware Information Server should set the security level settings in the Internet browser to “Medium – High” to minimize the risks presented by these vulnerabilities.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
- Minimize network exposure for all control system devices. Critical devices should not directly face the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.
The Control Systems Security Program (CSSP) also provides a section for control systems security recommended practices on the CSSP web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open unsolicited attachments in e-mail messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding e-mail scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
- 1http://cwe.mitre.org/data/definitions/79.html, website last accessed March 29, 2012.
- 2National Vulnerability Database Calculator for LFSEC00000069, website last accessed March 29, 2012.
- 3http://cwe.mitre.org/data/definitions/89.html, website last accessed March29, 2012.
- 4National Vulnerability Database Calculator for LFSEC00000069, website last accessed March 29, 2012.
- 5http://cwe.mitre.org/data/definitions/264.html, website last accessed March 29, 2012.
- 6National Vulnerability Database Calculator for LFSEC00000069, website last accessed March 29, 2012.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.