All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
OVERVIEW
ICS-CERT has been actively investigating and reporting on the Stuxnet vulnerability. To date, ICS-CERT has released ICSA-10-201-01 - Malware Targeting Siemens Control Software (including Updates B & C) and ICSA-10-238-01 - Stuxnet Mitigations (including Update B).
Stuxnet uses four zero-day exploits (two of which have been patched) and takes advantage of a vulnerability also exploited by Conficker, which has been documented in Microsoft Security Bulletin MS-08-067.a The known methods of propagation include infected USB devices, network shares, STEP 7 Project files, WinCC database files, and the print spooler vulnerability addressed by MS-10-061.b The malware can be updated through a command and control infrastructure as well as peer-to-peer communication using the Remote Procedure Call (RPC) protocol.
The malware also interacts with Siemens SIMATIC WinCC or SIMATIC STEP 7 software. Exact software versions and configurations that may be affected are still being analyzed jointly by ICS-CERT and Siemens. We have listed the following indicators for use in detecting this malware.
PRIMARY MALWARE INDICATORS
INDICATOR LIST OVERVIEW
The following indicator list was developed by ICS-CERT and will be useful in detecting malicious files in systems infected with Stuxnet. Tests were performed on two systems. One system was a new installation of Windows XP SP3 that was subsequently infected with Stuxnet. The other machine was the same Windows configuration but also included Siemens WinCC and STEP 7 software installations. Based on these tests, ICS-CERT has determined that these indicators fall into two groups. Some indicators appear on systems whether or not they have Siemens WinCC/STEP 7 installed, and the others only appear on systems with WinCC/STEP 7 installed.
INFECTED MACHINES WITH/WITHOUT WINCC/STEP 7 INSTALLED
Filename and Path | Hash |
WINDOWS\inf\mdmeric3.PNF | b834ebeb777ea07fb6aab6bf35cdf07f |
WINDOWS\inf\oem6C.PNF | Hash may vary |
WINDOWS\inf\oem7A.PNF | ad19fbaa55e8ad585a97bbcddcde59d4 |
WINDOWS\inf\mdmcpq3.PNF | Hash may vary |
WINDOWS\system32\drivers\mrxcls.sys | f8153747bae8b4ae48837ee17172151e |
WINDOWS\system32\drivers\mrxnet.sys | cc1db5360109de3b857654297d262ca1 |
INFECTED MACHINES WITH WINCC/STEP 7 INSTALLED
Filename and Path | Hash |
WINDOWS\system32\s7otbxdx.dll (malicious file has the same name as the original legitimate STEP 7 file) | 7a4e2d2638a454442efb95f23df391a1 |
WINDOWS\system32\s7otbxsx.dll (this is the original legitimate STEP 7 file which has been renamed by the malware) | 5b855cff1dba22ca12d4b70b43927db7 |
The following files may be found in WinCC/STEP7 Project directories.
Filename and Path | Hash |
\GraCS\cc_alg.sav | ad19fbaa55e8ad585a97bbcddcde59d4 |
\GraCS\cc_tag.sav | Hash may vary |
\GraCS\cc_tlg7.sav | d102bdad06b27616babe442e14461059 |
\GraCS\db_log.sav | b834ebeb777ea07fb6aab6bf35cdf07f |
In infected projects, the malicious *.sav files are stored in the GraCS subdirectory within a project’s root directory. This can occur in compressed or zipped project files. It appears that the malware specifically looks for demo projects commonly installed as part of the WinCC software. If any of these malicious *.sav files are found, it is likely that the malware has injected malicious stored procedures into one or more of the project’s database files. If any of these malicious *.sav files are detected, please contact ICS-CERT for further assistance.
MITIGATION
For information regarding Stuxnet mitigations, please refer to ICSA-10-238-01B – Stuxnet Mitigations.
Organizations should follow their established internal procedures if any suspected malicious activity is observed and report their findings to ICS-CERT for tracking and correlation against other incidents. ICS-CERT reminds organizations that proper impact analysis and risk assessment should be performed prior to taking defensive measures.
The Control System Security Program also provides a recommended practices section for control systems on the US-CERT website. Several recommended practices are available for reading or download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Contact Information
For any questions related to this report, please contact the CISA at:
Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.